HP HPE G2 Series User Manual page 140

Metered, switched, and metered & switched power distribution unit
Table of Contents

Advertisement

dev outlet <PDUID> status
Description
Query all outlet status with specified PDUID.
Example
HPE>Dev outlet 1 status
E000
Relay outlet status
Outlet#1: Close Outlet#2: Close Outlet#3: Close
Close
Outlet#4: CLose
Outlet#5: Close Outlet#6: Close Outlet#7: Close
Outlet#8: Close
Outlet#9 Close Outlet#10: Close Outlet#11:
Close
Outlet#12: Close
NOTE: This command is invalid for Metered PDUs.
NOTE: PDUIDs increment from 1. If in daisy chain mode, the master PDUID is 1 and the slave PDUIDs are 2
and 3.
dev outlet <PDUID> <outlet index> [on|off]
Description
Query or set specified PDUID and outlet status.
Example
HPE>Dev outlet 1 1 off
E000
NOTE: This command is invalid for Metered PDUs.
dev sensor
Description
List all sensors equipped.
Example output
HPE>dev sensor
E000
Sensor count 4
-----------------
Name Type, SN Value
T1, TEMP 012345678 27.5
T3, TEMP 012345678 27.2
T2, TEMP 012345678 27.3
RH HUMI
140
Appendix
012345678 44