Configuring HPE SIM to Receive Traps

Prerequisites
Before SIM can receive traps, the correct MIB file (cpqpower.mib) must be compiled into SIM. To download
the Power MIB, visit the Hewlett Packard Enterprise website http://www.hpe.com/info/rackandpower.
Procedure
1. Copy the MIB file to the HPE\Systems Insight Manager\mibs folder.
2. From the HPE\Systems Insight Manager\mibs folder, run mcompile cpqpower.mib from the
command line to compile the new MIB. A new file named cpqpower.cfg is created.
3. Register the new MIB by entering mxmib -a cpqpower.cfg from the HPE\Systems Insight
Manager\mibs command line.
4. Enter HPE\Systems Insight Manager\mibs>mxmib at the command line and verify that the new MIB
is listed.
NOTE: For more information on uploading and registering the MIB in SIM, see the Insight Manager
technical reference guide on the Hewlett Packard Enterprise management CD.

Configuring the PDU to Send Traps to SIM

Procedure
1. On the PDU web interface, click the Setup tab.
2. Click the Remote Management menu.
3. Add the SIM server as an SNMP trap recipient on the Trap Receivers tab.
4. Configure the PDU to send alert notifications to SIM on the Event Notifications tab.