05.01
9.2.5

Timing diagram for the ready signal in the I/R module

Load
supply
available
T. 48
T. 64
T. 63
Ready
A
T. 72...74
Fig. 9-4
Timing diagram for the ready signal in the I/R module
Switch S1.2 = OFF, standard setting at the I/R module "Ready signal"
A
The ready relay can only pull in if the pre–charging sequence has been comple-
ted and the internal line contactor has pulled in.
B
The I/R module is internally inhibited during power failures, i.e. the I/R module
can no longer control (closed–loop) the DC link voltage which means that bra-
king energy can no longer be fed back into the line supply. The drives are not
inhibited, but the ready relay drops out with a delay, after the line failure detec-
tion time, dependent on the line impedances.
C
When the load supply is disconnected using the main switch or an external line
contactor, e.g. for a six–conductor connection (refer to Section 9.13) as well as
other switching elements, it must be ensured, that at least 10 ms beforehand,
terminal 48 at the I/R module is de–energized. This can be achieved, e.g. using
a main switch with leading contact or interlocking circuits for the external line
contactor or other switching elements.
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
Shutdown using the main switch, external line
contactor or another switching element.
Supply voltage
A
A
9 Important Circuit Information
9.2 Infeed modules
Supply failure
Supply voltage
B
C
A
A
9
9-231