9 Important Circuit Information

9.2 Infeed modules

9.2
9.2.1
Only PELV circuits may
be connected to terminal
19 (FR–).
Additional
terminal 19
Additional
terminal 48
9
2)
Leading
contact
Fig. 9-2
9-222
Infeed modules
Three–conductor connection (standard circuit)
X111
X121
63
9
9
64
19
X141
Pushbutton
15
contact
R
9
X161
112
1)
48
111
213
113
X171
NS 1
1)
NS
2
X172
AS1
AS2
LEDs
X181
M500
P500
2U1
1)
1U1
2V1
1)
1V1
2W1
1)
1W1
U1
1U2
Reactor, only for
I/R module and
UI 28 kW
U
Line filter
L1
Line fuses for I/R
or UI module, refer
to Section 7.1.1
Main switch
Supply
L1
Three–conductor connection (standard circuit)
S1
NE–module,
2)
(with the excep-
tion UI 5 kW)
Electronics
Power
power sup-
section
ply
A
B
L+
A
B
V1
1 W
L1
L2
X131
1V2
1W2
3)
F1
F2
Notice
1) Jumpers when the equipment is supplied.
Depending on the particular application, re-
V
W
move the jumpers (refer to the circuit exam-
Z
ples, Section 9.7.).
L2
L3
2) For I/R modules with a setting for closed–
loop controlled operation, the following applies
(refer to switch S1, Section 6)
terminal 48 mustw be de–energized 10 ms
before the main switch line contacts open (e.g.
PE
leading contact).
3) Terminals L1,L2 are only available for I/R
modules 80 and 120 KW.
4) Grounding bar open when supplied.
L2
L3
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
05.01
L–
Internal line
contactor
To the drive
modules
P600
P600
To the drive
modules
4)
M600
M600
100 k
PE
to the
NC
 Siemens AG 2001 All rights reserved

Hide quick links:

Advertisement

Table of Contents
loading