Interface Overview, 5 Kw Ui Module - Siemens SIMODRIVE 611 Planning Manual

Drive converter
Hide thumbs Also See for SIMODRIVE 611:
Table of Contents

Advertisement

6 Infeed Modules
6.4 Interface overview
6.4.2
Table 6-7
Term.
No.
U1
V1
W1
PE –
P600
M600
M500
6
P500
1U1
2U1
1V1
2V1
1W1
2W1
5.3
5.2
5.1
nc
74
73.2
73.1
72
2)
63
2)4)
9
2)4)
9
2)
64
5)
R
19
_________
1)
2)
3)
4)
5)
6)
6-180

Interface overview, 5 kW UI module

Interface overview, 5 kW UI module
Desig.
Function
X1
Supply connection
Protective conductor
X131
Electronics M
X351
Equipment bus
3)
Grounding bar
DC link
X181
DC link power supply
X181
DC link power supply
X181
Output L1
X181
Input L1
X181
Output L2
X181
Input L2
X181
Output L3
X181
Input L3
X121A
Relay contact
X121A
group signal
X121A
2
I
t/motor temp.
X121A
X121B
Relay signal
X121B
Ready/fault
X121B
X121B
X141AX
Pulse enable
141A
FR+
X141A
FR+
X141A
Drive enable
X141A
RESET
X141A
FR, reference ground enable
voltage
I = input; O = output; NC = NC contact; NO = NO contact
Terminal 19 is the reference terminal (connected in the module to 10 kW to general reference ground X131)
Terminal 15 may neither be connected to PE nor to terminal 19, furthermore, it is not permissible that external
voltage sources are connected to terminal 15. Terminal 19 may be connected to terminal X131.
The terminal may only be used to enable the associated drive group.
The grounding bar is used to ground the DC link M rail through 100 kΩ (this should be preferably inserted;
if the system is subject to a high–voltage test, the grounding bar should be opened).
Max. current load of terminal 9 - terminal 19  1 A
Notice: UI 5 kW does not have terminals 7, 45, 44 and 10.
RESET = Reset the fault memory, edge triggered for the complete drive group
(term. "R" ! term. 19 = RESET)
For UL certification, only use copper cables designed for an operating temperature of w 60°C
Type
Typ. voltage/limit values
1)
I
3–ph. 400 V AC
I
0 V
I
0 V
I/O
Various
I/O
–300 V
I/O
+300 V
–300 V
I
–300 V
I
+300 V
O
3–ph. 400 V AC
I
3–ph. 400 V AC
O
3–ph. 400 V AC
I
3–ph. 400 V AC
O
3–ph. 400 V AC
I
3–ph. 400 V AC
NC
50 V DC/0.5 A/12 VA max
NO
5 V DC/3 mA min
I
NC
1AC 250 V/DC 50 V/2 A max
I
I
1DC 5 V/3 mA min
NO
I
+13 V...30 V/R
= 1.5 kΩ
E
O
+24 V
O
+24 V
I
+13 V...30 V/R
= 1.5 kΩ
E
I
term.19/R
= 10 kΩ
E
O
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
05.01
Max. cross–section
6)
2
4 mm
finely stranded
without end sleeves
2
6 mm
with cable lug
M5 thread
M4 thread
34–core ribbon cable
Busbar
Busbar
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents