Siemens SIMODRIVE 611 Planning Manual page 200

Drive converter
Hide thumbs Also See for SIMODRIVE 611:
Table of Contents

Advertisement

6 Infeed Modules
6.6 DC link options
Mounting
positions
6
6-200
Horizontal and vertical mounting positions are possible.
Connection for external pulsed resistor 0.3/25 kW
Order number: 6SN1113–1AA00–0DA0
Red, blue, PE (green, yellow) each 1.5 mm
Shielded 3 m connecting cable, can be extended up to 10 m
Fig. 6-14
Connection for external pulsed resistor 0.3/25 kW
Connection for external pulsed resistor 1.5/25 kW
Order number: 6SN1113–1AA00–0CA0
3R
1R
Shield connection is realized through the PG gland
Shielded connecting cable (braided screen) cross–section 2.5 – 4 mm
max. length 10 m
Fig. 6-15
Connection for external pulsed resistor 1.5/25 kW
Note
Conductors which are not used in multi–conductor cables must always be con-
nected to PE at both ends.
PE
PE
 Siemens AG 2001 All rights reserved
SIMODRIVE 611 Planning Guide (PJU) – 05.01 Edition
05.01
2
2