Digital in- and output module UR20-4DI-4DO-PN-FSPS, UR20-4DI-4DO-PN-FSPS-V2

Digital input and output module UR20-4DI-4DO-PN-FSPS (Order No. 1335060000),
UR20-4DI-4DO-PN-FSPS-V2 (Order No. 2464570000)
The digital input and output module UR20-4DI-4DO-PN-FSPS
or UR20-4DI-4DO-PN-FSPS-V2 is a safe I/O module for the
PROFIsafe protocol. Each module provides four digital inputs
and outputs respectively, it can detect up to four binary
control signals and control up to four actuators each with a
maximum of 0.5 A. Two inputs and outputs respectively can
be parameterised P- or N-switching.
Sensors can be connected to connectors 1 and 2 using a
2-wire, 3-wire or 4-wire connection. In the event that the
available supply current of 0.8 A per plug will not suffice, the
sensor supply must be realised using the auxiliary outputs
of another module (e.g. potential distribution module) within
the same power segment.
Actuators can be connected to connectors 3 and 4 using a
2-wire connection. A status LED is assigned to each channel.
The module electronics supply the inputs as well as the out-
puts with power from the output current path (I
A test pulse check of the inputs can be parameterised as a
cross-circuit detection between input singal and supply volt-
age, between different input signals or other signals. Thus an
input gets active only when the signal of the dedicated aux-
iliary output is pending. The test pulses must be disabled if a
safety relay with OSSD outputs generating own test pulses is
connected.
1484600000/04/06.2017
5 Detailed descriptions of safe modules | Digital in- and output module UR20-4DI-4DO-PN-FSPS, UR20-4DI-4DO-PN-FSPS-V2
).
OUT
u-remote IP20 modules for functional safety manual
4DI·4DO
1
DI 0 (PN)
2
AUX-O 0
1
3
AUX-O 1
4
DI 1 (P)
1
DI 2 (PN)
2
AUX-O 2
2
3
AUX-O 3
4
DI 3 (P)
1
DO 0 (PN)
2
GND
3
3
DO 1 (P)
4
GND
1
DO 2 (PN)
2
GND
4
3
DO 3 (P)
4
GND
Connection diagram UR20-4DI-4DO-PN-FSPS , UR20-4DI-4DO-PN-FSPS-V2
With the variant 1 module the active output signal always
includes test pulses for the purpose of cross-circuit and error
detection. The test pulse duration can be parameterised.
A safety sensor that is being connected in a dual chan-
nel mode (safety architecture of category 4 acc. to
DIN EN ISO 13849) must allocate the PN and the P-input of
one connector.
The external circuitry of a PN/P output pair is described in
Chapter 3.
4DI·4DO
1
DI 0 (PN)
Safety relay
GND
2
AUX-O 0
with OSSD
1
24 V DC
3
AUX-O 1
outputs
4
DI 1 (P)
1
DI 2 (PN)
2
AUX-O 2
2
3
AUX-O 3
4
DI 3 (P)
1
DO 0 (PN)
2
GND
3
3
DO 1 (P)
4
GND
1
DO 2 (PN)
2
GND
4
3
DO 3 (P)
4
GND