Type of connection
Line connection cross-section
Dimensions
Protection class (DIN EN 60529)
Flammability rating UL 94
Temperature data
Humidity
Air pressure
Vibration resistance
Shock resistance
Potential isolation
Approvals and Standards
1)
Unless otherwise noted within the product-specific technical data.
1)
You can find all product-specific technical data in the corresponding product description.
1484600000/04/06.2017
"PUSH IN"
Single-wired
Fine-wired
Height
Width
Depth
IP20
V-0
Operation
Storage, transport
Operation, storage, transport
Operation
Storage, transport
5 Hz ≤ f ≤ 8.4 Hz: 3.5-mm amplitude as per IEC 60068-2-6
8.4 Hz ≤ f ≤ 150 Hz: 1-g acceleration as per IEC 60068-2-6
15 g for 11 ms, half sinewave, as per IEC 60068-2-27
Test voltage
Pollution severity level
Overvoltage category
UL
c
us
Potentially explosive atmosphere Zone 2
EMC
Explosion protection
PLC
FS
u-remote IP20 modules for functional safety manual
5 Detailed descriptions of safe modules | General technical data
0.14 – 1.5 mm
(AWG 16 – 26)
2
0.14 – 1.5 mm
(AWG 16 – 26)
2
120 mm (128 mm with release lever)
11.5 mm
76.0 mm
-20 °C to +60 °C
-40 °C to +85 °C
5 % to 95 %, non-condensing as per IEC 61131-2
≥ 795 hPa (altitude ≤ 2000 m)  as per IEC 61131-2
≥ 700 hPa (altitude ≤ 3000 m)  as per IEC 61131-2
Max. 28.8 V within a channel
500 V DC field/system
2
II
UL 508 pending
ATEX Directive 2014/34/EU
EN 61000 (Partial standards as per requirements of IEC 61131-2)
EN 60079-0:2009 and EN 60079-15:2010
IEC 61131-2
DIN EN ISO 13849-1, IEC 61508, IEC 62061