Sample Design - Weidmuller UR20-4DI-4DO-PN-FSOE Manual

Remote i/o system u-remote; modules for functional safety
Table of Contents

Advertisement

4 System description of safe power-feed modules | Sample design
4.1

Sample design

The following picture exemplifies how to design a safety seg-
ment using a safe power-feed module. All output modules
arranged within the safety segment will be switched safely.
Input modules can be arranged within the safety segment,
only they do not fulfill any safety function and are not influ-
enced by the PF-O-xDI-SIL module.
Safe I/O modules with outputs may not be posi-
tioned within a safety segment.
For detailed planning please also observe the
notes in the section „Configuration".
Example set-up of a safety segment (1) with PF-O-xDI-SIL
16
FB
U
24 V
IN
24 V
U
24 V
OUT
u-remote IP20 modules for functional safety manual
To switch the 24 V Safe voltage back on, either an automatic
or a manual start can be selected.
– Automatic start: the safe output current path is switched
on immediately after resetting the safety circuit(s).
– Manual start: the output current path is only switched on
again if the start button has been held down for 0.5 to
2 seconds.
1
PF-O
SIL
DI
DO
DO
AO DO
DI
U
24 V Safe
OUT
24 V
WARNING
Possible danger to life!
The option "Automatic start" might only be
used, after a risk analysis has shown that the
application is suitable.
PF-O
DO
DO
DO
DI
24 V
1484600000/04/06.2017