Weidmuller UR20-4DI-4DO-PN-FSOE Manual page 68

Remote i/o system u-remote; modules for functional safety
Table of Contents

Advertisement

5 Detailed descriptions of safe modules | Safe power-feed module UR20-PF-O-2DI-DELAY-SIL
Technical data UR20-PF-O-2DI-DELAY-SIL Order No. 1335040000)
Auxiliary outputs
Output current
Diagnosis
Module diagnosis
Individual channel diagnosis
Supply
Supply voltage
External pre-fusing
Reverse battery protection
Current consumption from system current path I
Current consumption from input current path I
General data
Weight (operational status)
Additional general data, see Section 5.1
Prozess data UR20-PF-O-2DI-DELAY-SIL
Byte
Bit
0
1
2
3
0
4
5
6
7
0
1
1
2
3 ... 7
2
0 ... 7
0
1
3
2
3
4 ... 7
68
SYS
IN
Description
Safety Input 0
Safety Input 1
Automatic start
Manual start
Safety Input 0, Channel 1
Safety Input 0, Channel 2
Safety Input 1, Channel 1
Safety Input 1, Channel 2
24 V Safe output
SS1 output
24 V feed-in
reserved
reserved
DIP-Switch configuration
DIP-Switch configuration
DIP-Switch configuration
reserved
u-remote IP20 modules for functional safety manual
3 x 2
Max. 10 mA (only to support the inputs dedicated inputs)
yes
yes
24 V DC +20 %/-15 %
Mandatory: super fast, max. 8 A
yes
8 mA
45 mA
84 g
Status
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - inactive, 1 - active
0 - no feed-in, 1 - power feed-in pending
Safety input 0: 0 - Pulse,1 - No Pulse
Safety input 1: 0 - Pulse,1 - No Pulse
24 V Safe output: 00 - No delay, 01 - Delay 1 s, 10 - Delay
30 s, 11 - Delay 60 s
Connection
S 11 ... S 22
S 31 ... S 42
Autostart 1/2
Man Start 1/2
S 11/S 12
S 21/S 22
S 31/S 32
S 41/S 42
24 V Safe
SS 1
24 V
1484600000/04/06.2017

Hide quick links:

Advertisement

Table of Contents
loading