3.4
Registration of safe I/O modules on the
safety control
Safe I/O modules need to get registered on a safety control
using an engineering tool. Via the web server the safe I/O
modules can only be observed but not be parameterised or
forced.
PROFIsafe
For the commissioning of safe I/O modules running with the
PROFIsafe safety protocol you will need the Weidmüller CPD
tool which is available to download on the website. Accord-
ing to the parameter settings this software tool calculates a
check sum, wich will be transferred to the safety control in
Siemens STEP7 and on the TIA portal.
Fail-Safe-over-EtherCAT
For the commissioning of safe I/O modules running with
the Fail safe over EtherCAT safety protocol you will need
TwinCAT as well as a TwinSAFE safety control. The FSOE
modules have been tested using the TwinSAFE-Logic
EL6900 system (Beckhoff) and TwinCAT 2.11.2247
(Beckhoff).
3.5

Safety address

Before commissioning the safety address (F-address) has to
be set on each safe I/O module using the DIP switches on
the electronic unit. This address is indicated by the project
planning. The safety control transfers the safety address to
the module on each commissioning.
The safety address (decimal) has to be converted into a bi-
nary value and then set using the DIP switches .
Decimal/binary conversion table
decimal
2048 1024
512
256
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
binary
0
0
0
0
0
0
0
0
0
0
0
1
0
0
1
0
0
1
0
0
1
0
0
0
1234
0
1
0
0
Example: Address „1234" is represented by setting
0000010011010010.
1484600000/04/06.2017
3 System description of safe I/O modules | Registration of safe I/O modules on the safety control
128
64
32
16
8
4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
0
1
0
0
u-remote IP20 modules for functional safety manual
Please use e.g. a ball pen to set the DIP switches
and avoid sharp-edged tools.
With PROFIsafe modules: Make sure that switch-
es without identification marking always remain
in position "Zero".
Setting the safety address
▶ Before snapping the module onto the DIN rail please set
the safety address according to the project planning via
the DIP switches on the electronic unit.
▶ Snap the module onto the DIN rail and continue the
installation of the u-remote station.
DIP switches for setting the safety address on a PROFIsafe module (example setting: 1234)
Changing the safety address
To change the safety address after the module has been as-
2
1
signed to the control please act as follows (with V2 modules
0
1
start with step 5):
1
0
1. Pull out the electronic unit.
0
0
2. Set all DIP switches to position „Zero".
0
0
3. Slide the electronic unit back into the module and turn on
0
0
the module/station.
0
0
4. Please wait until the status LED of the module lights alter-
0
0
nating red and green (3 s green, 1 s red).
0
0
Only now the old safety address has been deleted and the
0
0
new one can be set.
0
0
5. Pull out the electronic unit again and set the new safety
0
0
address.
0
0
6. Slide the electronic unit back into the module and turn on
1
0
the module/station.
The status LED of the module lights green and the new safe-
ty address will be displayed on the web server.
1 0