Modules Switchable By Pf-O-Xdi-Sil; Configuration; Switch-Off Delay Time - Weidmuller UR20-4DI-4DO-PN-FSOE Manual

Remote i/o system u-remote; modules for functional safety
Table of Contents

Advertisement

4 System description of safe power-feed modules | Modules switchable by PF-O-xDI-SIL
4.3

Modules switchable by PF-O-xDI-SIL

Safely switchable output modules:
– UR20-4DO-P
– UR20-4DO-P-2A
– UR20-4DO-PN-2A
– UR20-8DO-P
– UR20-8DO-P-2W-HD
– UR20-16DO-P
– UR20-16DO-P-PLC-INT
– UR20-4DO-N
– UR20-4DO-N-2A
– UR20-8DO-N
– UR20-2PWM-PN-0.5A
– UR20-2PWM-PN-2A
– UR20-4AO-UI-16
– UR20-4AO-UI-16-HD
– UR20-4AO-UI-16-DIAG
– UR20-4AO-UI-16-DIAG-HD
In case a N-switching output module is positioned within a
safety segment the connected load needs to be switched
against +24 V Safe.
The relay output modules UR20-4RO-CO-255 and UR20-
4RO-SSR-255 are not safely switchable, therefore they must
not switch any safety function.
The digital counter module UR20-1CNT-1DO-100 will not be
switched since it is supplied via the input current path.
4.4

Configuration

A PF-O-xDI-SIL module can be positioned anywhere in
the u-remote station. Multiple PF-O-xDI-SIL modules
and thus safety segments can be set up in a single station.
When planning a u-remote station with PF-O-xDI-SIL
modules, the following requirements must be met:
– The overall current consumption from the system current
path of all switchable modules within a safety segment
must be lower than 100 mA (see table in section 4.5).
– Each safety segment might include at most 12 switcha-
ble modules.
– The switch-off delay time for the safe input channels
within a safety circuit is 500 ms ± 10 ms.
– The load output is not designed for either inductive or
capacitive loads.
– The feed-in of the PF-O-xDI-SIL module must be
safeguarded with a 8-A super fast fuse.
– A SELV/PELV power supply must be used.
– The safely shut-off systems/applications must get their
power exclusively from the safe feed-in module
PF-O-xDI-SIL. Likewise, it must not be possible to
feed external energy into the safety segment elsewhere.
18
– Relay modules can be located within a safety segment,
however their outputs cannot be safely shut off in case of
a malfunction.
– At the SS1 output of the UR20-PF-O-2DI-DELAY-SIL, only
systems/equipment that do not feed any power back into
the system in the event of a malfunction can be con-
nected.
– Any external short circuits in the wiring of the safe output
must be avoided.
– Fault exclusion as per EN ISO 13849-2 must be provided.
4.5

Switch-off delay time

The turn-off time of a PF-O-xDI-SIL module is 20 ms,
caused by the hardware and firmware delay time. The time
required until the output voltage even of the last switchable
module of a safety segment is below 5 V, can be calculated
as follows:
Turn-off time of a PF-O-xDI-SIL module
+ Sum of all modules' hardware delay
= Switch off delay [ms]
Switch-off delay and current consumption
UR20-4DO-P
UR20-4DO-P-2A
UR20-4DO-PN-2A
UR20-8DO-P
UR20-8DO-P-2W-HD
UR20-16DO-P
UR20-16DO-P-PLC-INT
UR20-4DO-N
UR20-4DO-N-2A
UR20-2PWM-PN-0.5A
UR20-2PWM-PN-2A
UR20-4AO-UI-16
UR20-4AO-UI-16-HD
UR20-4AO-UI-16-DIAG
UR20-4AO-UI-16-DIAG-HD
*The delay time is always 150 ms, irrespective of the amout of these modules.
u-remote IP20 modules for functional safety manual
Hardware delay [ms]
Current consumption
from I
SYS
2
2
3
1
1
1
1
2
2
5
5
150*
150*
150*
150*
1484600000/04/06.2017
[mA]
8
8
15
15
15
10
10
8
8
10
10
10
10
10
10