Weidmuller UR20-4DI-4DO-PN-FSOE Manual page 28

Remote i/o system u-remote; modules for functional safety
Table of Contents

Advertisement

5 Detailed descriptions of safe modules | Digital in- and output module UR20-4DI-4DO-PN-FSOE, UR20-4DI-4DO-PN-FSOE-V2
Technical data UR20-4DI-4DO-PN-FSOE (Order No. 1529780000), UR20-4DI-4DO-PN-FSOE-V2 (Order No. 2464580000)
Supply
Supply voltage
Current consumption from system current path I
Current consumption from output current path I
General data
Weight (operational status)
Additional general data, see Section 5.1.
Overview of the editable parameters
Channel
Description
0 ... 1
Input delay
0 ... 1
Test pulse
0
Input polarity
0 + 1
Input dual channel mode (inputs 0 + 1)
0 + 1
Discrepancy time
2 ... 3
Input delay
2 ... 3
Test pulse
2
Input polarity
2 + 3
Input dual channel mode (inputs 2 + 3)
2 + 3
Discrepancy time
4 ... 5
Output test pulse duration (output 0 ... 1)
4
Output polarity
4 + 5
Output dual channel mode (outputs 0 + 1)
6 ... 7
Output test pulse duration (output 2 ... 3)
6
Output polarity
6 + 7
Output dual channel mode (outputs 2 + 3)
1) Please regard the notes for parameter settings.
Overview of the editable parameters
Channel
Description
0 
Input delay
0 
Test pulse
0
Input polarity
1
Input delay
1
Test pulse
1) Please regard the notes for parameter settings.
28
24 V DC +20 %/-15 %
8 mA
SYS
20 mA + output current + current consumption from the auxiliary outputs
OUT
93 g
UR20-4DI-4DO-PN-FSOE
1)
Options
1 ms (0) / 3 ms (1) / 10 ms (2) / 100 ms (3)
disabled (0) / enabled (1)
P-switching (0) / N-switching (1)
single channel (0) / dual channel (1)
5 ms (0) / 50 ms (1) / 2 s (2) / 30 s (3)
1 ms (0) / 3 ms (1) / 10 ms (2) / 100 ms (3)
disabled (0) / enabled (1)
P-switching (0) / N-switching (1)
single channel (0) / dual channel (1)
5 ms (0) / 50 ms (1) / 2 s (2) / 30 s (3)
0.5 ms (0) / 1 ms (1) / 3 ms (2) / 10 ms (3)
P-switching (0) / N-switching (1)
single channel (0) / dual channel (1)
0.5 ms (0) / 1 ms (1) / 3 ms (2) / 10 ms (3)
P-switching (0) / N-switching (1)
single channel (0) / dual channel (1)
UR20-4DI-4DO-PN-FSOE-V2
1)
Options
1 ms (0) / 3 ms (1) / 10 ms (2) / 100 ms (3)
internal (0) / external (1) / from AUX0 (2) / from AUX1 (3)
P-switching (0) / N-switching (1)
1 ms (0) / 3 ms (1) / 10 ms (2) / 100 ms (3)
internal (0) / external (1) / from AUX0 (2) / from AUX1 (3)
u-remote IP20 modules for functional safety manual
Default
1 ms
disabled
P-switching
single channel
5 ms
1 ms
disabled
P-switching
single channel
5 ms
0.5 ms
P-switching
single channel
0.5 ms
P-switching
single channel
Default
1 ms
internal
P-switching
1 ms
internal
1484600000/04/06.2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents