Weidmuller UR20-4DI-4DO-PN-FSOE Manual page 35

Remote i/o system u-remote; modules for functional safety
Table of Contents

Advertisement

Technical data UR20-8DI-PN-FSOE (Order No. 1529800000), UR20-8DI-PN-FSOE-V2 (Order No. 2464600000)
Sensor connection
Reverse polarity protection
Module diagnosis
Individual channel diagnosis
Supply
Supply voltage
Current consumption from system current path I
Current consumption from output current path I
General data
Weight (operational status)
Additional general data, see Section 5.1.
1) Minimum rate of change in transition range: 1 V/s. Deviating from EN 61131-2 the following applies for PN-inputs in P-switching mode:The input will be read "inactive" if the input
voltage considerably exceeds the module supply voltage.
Overview of the editable parameters
Channel
Description
0 ... 1
Input delay
0 ... 1
Test pulse
0
Input polarity
0 + 1
Input dual channel mode (inputs 0 + 1)
0 + 1
Discrepancy time
2 ... 3
Input delay
2 ... 3
Test pulse
2
Input polarity
2 + 3
Input dual channel mode (inputs 2 + 3)
2 + 3
Discrepancy time
4 ... 5
Input delay
4 ... 5
Test pulse
4
Input polarity
4 + 5
Input dual channel mode (inputs 4 + 5)
4 + 5
Discrepancy time
6 ... 7
Input delay
6 ... 7
Test pulse
6
Input polarity
6 + 7
Input dual channel mode (inputs 6 + 7)
6 + 7
Discrepancy time
1) Please regard the notes for parameter settings.
1484600000/04/06.2017
5 Detailed descriptions of safe modules | Digital input module UR20-8DI-PN-FSOE, UR20-8DI-PN-FSOE-V2
2-wire, 3-wire, 4-wire
yes
yes
yes
24 V DC +20 %/-15 %
8 mA
SYS
20 mA + output current + current consumption from the auxiliary outputs
OUT
93 g
UR20-8DI-PN-FSOE
1)
Options
1 ms (0) / 3 ms (1) / 10 ms (2) / 100 ms (3)
disabled (0) / enabled (1)
P-switching (0) / N-switching (1)
single channel (0) / dual channel (1)
5 ms (0) / 50 ms (1) / 2 s (2) / 30 s (3)
1 ms (0) / 3 ms (1) / 10 ms (2) / 100 ms (3)
disabled (0) / enabled (1)
P-switching (0) / N-switching (1)
single channel (0) / dual channel (1)
5 ms (0) / 50 ms (1) / 2 s (2) / 30 s (3)
1 ms (0) / 3 ms (1) / 10 ms (2) / 100 ms (3)
disabled (0) / enabled (1)
P-switching (0) / N-switching (1)
single channel (0) / dual channel (1)
5 ms (0) / 50 ms (1) / 2 s (2) / 30 s (3)
1 ms (0) / 3 ms (1) / 10 ms (2) / 100 ms (3)
disabled (0) / enabled (1)
P-switching (0) / N-switching (1)
single channel (0) / dual channel (1)
5 ms (0) / 50 ms (1) / 2 s (2) / 30 s (3)
u-remote IP20 modules for functional safety manual
Default
1 ms
disabled
P-switching
single channel
5 ms
1 ms
disabled
P-switching
single channel
5 ms
1 ms
disabled
P-switching
single channel
5 ms
1 ms
disabled
P-switching
single channel
5 ms
35