Chapter 3: Configuration and Commissioning
Option
SN Poll Timeout [1]
SN+ Looped Bus [2]
Leg. Time Sync [1]
2nd Cmd Module [1]
[1] Command modules only.
[2] Minimum and standard display modules only.
To configure the network:
1. Select Communications from the Main menu, and then select Network Setup.
2. Enter your configuration changes.
3. Press F1 (Save) to save your changes and exit to the previous screen.
4. If you have no other configuration changes to make, then press F1 (Apply)
from the Main menu or the submenu to apply the changes to the system.
Using a secondary command module
Two command modules can be included in a SenseNET network to provide
redundancy, if required.
The first command module acts as the primary module, controlling and
monitoring the network, while the second command module remains in listening
mode. When the second command module detects that the primary command
module is not operational, it assumes control of the network.
Notes:
This option only applies to command modules. It must be disabled in the
primary command module and enabled in the secondary command module.
If the primary command module is recovered, then the secondary module
returns to listening mode.
The primary command module configures the secondary command module
remotely. It appears in the device list after a network scan.
68
Description
Configures the maximum response time (in milliseconds) for
a SenseNET status query.
Warning: Do not exceed the maximum recommended
settings included in "Configuring the Poll Timeout setting" on
page 69.
Configures the SenseNET+ protocol. If checked, the cluster
uses a Class A closed loop topology.
Configures the date and time synchronization for legacy
detectors in the network. If checked, the date and time in
legacy detectors is synchronized with the command module.
Note: Date and time synchronization erases any chart
record information stored by the legacy detectors.
Configures the use of a second command module in a
SenseNET network where redundancy is required. If
checked, the command module acts as the secondary
command module.
See "Using a secondary command module" below for more
information.
ModuLaser Modular Aspirating Smoke Detector Installation Manual

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ModuLaser and is the answer not in the manual?

Questions and answers

Al Greco
March 13, 2025

does a system smoke detector require a box or can I mount it with just a ring

1 comments:
Mr. Anderson
March 13, 2025

The Edwards ModuLaser system requires a backplane to be fixed to the wall for installation. The detector and display modules are then mounted onto this backplane. This suggests that a simple ring mount is not sufficient for installation.

This answer is automatically generated

Table of Contents