To disable a device:
1. Select Enable/Disable from the Main menu.
2. Select and check the device that you want to disable or press F1 (Go To) to
search for a device by the device address.
3. Press F2 (Back) twice to return to the Main menu screen.
Enabling a previously disabled device
Caution:
To prevent accidental alarms when enabling a previously disabled
detector, first ensure that the detector output level (DLevel) is lower than the fire
levels (Alarm 2, Alarm, Prealarm, Alert) – press F1 (Status) from the home
screen to view the device status details.
To enable a previously disabled device:
1. Select Enable/Disable from the Main menu.
2. Select and uncheck the device that you want to enable or press F1 (Go To) to
search for a device by the device address.
3. Press F2 (Back) twice to return to the Main menu screen.
Access level 3 user operation and
configuration
This access level is restricted and is reserved for authorized users trained to
configure the detection system. The default access code for this level is 3333.
In addition to those tasks described in Access level 2 user operation and
configuration on page 41, this level lets you:
•
Configure the date and time.
•
Configure the device settings (inputs, outputs, etc.)
•
Configure the detection settings (alarm levels, delays, flow, etc.)
•
Configure the communications settings (network setup, etc.)
ModuLaser Modular Aspirating Smoke Detector Installation Manual
Chapter 3: Configuration and Commissioning
53
Need help?
Do you have a question about the ModuLaser and is the answer not in the manual?
Questions and answers
does a system smoke detector require a box or can I mount it with just a ring
The Edwards ModuLaser system requires a backplane to be fixed to the wall for installation. The detector and display modules are then mounted onto this backplane. This suggests that a simple ring mount is not sufficient for installation.
This answer is automatically generated