Chapter 3: Configuration and Commissioning
Notes
•
Output 1 is set to General Fault on display modules and is not configurable. If
the display is a command module, any fault detected by any device in the
SenseNET network will activate this output.
•
A display output configured with Local influence and an Alarm function will
activate if any applicable alarm type is detected by any detector in the cluster
(or SenseNET network, if the display is a command module).
•
When a function is enabled for a given output, any previous configuration
using that output is automatically disabled.
•
Outputs and output functionality for legacy devices may vary from those
described above. Refer to the corresponding device installation manual for
more information.
Saving and loading configuration files
Use the Load/Save menu to save a module configuration file, to load a module
configuration from a file, or to restore the cluster configuration after maintenance.
Note:
This option can be used to quickly copy a configuration from one device to
another.
To save a module configuration file:
1. Remove the display cover, insert a USB flash drive into the USB connector,
and replace the cover.
2. Select Device Settings from the Main menu, and then select Load/Save
Settings.
3. Select Save to File.
4. Select the device that you want to view or press F1 (Go To) to search for a
device by the device address.
The configuration file is saved as a comma separated (CSV) file to the
following folder on the USB flash drive:
_ASPIRATION\Config\
This folder is created automatically on the flash drive. The name of the saved
file takes the format:
AAA_YYYYMMDD_HHMM_TT.csv
Where AAA is the device address, YYYYMMDD is the current date, HHMM is
the current time, and TT is a the device type identification code.
5. Press F3 (Exit) to return to the Main menu.
60
ModuLaser Modular Aspirating Smoke Detector Installation Manual
Need help?
Do you have a question about the ModuLaser and is the answer not in the manual?
Questions and answers
does a system smoke detector require a box or can I mount it with just a ring
The Edwards ModuLaser system requires a backplane to be fixed to the wall for installation. The detector and display modules are then mounted onto this backplane. This suggests that a simple ring mount is not sufficient for installation.
This answer is automatically generated