Chapter 3: Configuration and Commissioning

The Reset menu

Performing a system reset
Use the Reset menu to perform a system reset on a single device or the whole
installation. System events that have not been resolved will continue to be
reported after reset.
Caution:
Investigate all fire alarms and faults before resetting the system.
To reset the detection system and clear system events:
1. Select Reset from the Main menu, and then select List of Devices or All
Devices.
Selecting List of Devices allows you to select specific modules to reset.
Selecting All Devices resets all modules on the loop.
2. Press Enter to reset the selected devices.
After the reset completes, the home screen is displayed.
Note:
Disablements and tests are not terminated by a reset.

The Enable/Disable menu

Disabling a device
Caution:
To prevent accidental alarms, only disable a device during scheduled
service or maintenance periods.
Use the Enable/Disable menu to disable a device. A disabled device does not
report alarms or faults (but logs them in the event log).
Notes:
A disabled device will activate any output configured as General Fault or Disable
to signal its non-functional status to the main fire alarm system.
If a disabled device loses power (due to a power failure), the device will be
enabled at power up.
Display modules in a cluster with any disabled device will also activate any
output configured as general fault.
A disabled detector continues to operate normally, but its events are not
indicated. For example, faults and alarms are detected but are not indicated (they
are added to the event log).
Note:
When a detector is disabled, the detector Warning LED is steady and the
disablement is confirmed on the display module LCD.
52
ModuLaser Modular Aspirating Smoke Detector Installation Manual

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ModuLaser and is the answer not in the manual?

Questions and answers

Al Greco
March 13, 2025

does a system smoke detector require a box or can I mount it with just a ring

1 comments:
Mr. Anderson
March 13, 2025

The Edwards ModuLaser system requires a backplane to be fixed to the wall for installation. The detector and display modules are then mounted onto this backplane. This suggests that a simple ring mount is not sufficient for installation.

This answer is automatically generated

Table of Contents