19.3

Analog Electronics Modules with HART

Analog Input Modules with HART
Process image input table PII per module:
IB x
IB x+1
IB x+2
IB x+3
Example: Input value channel 0: 61A8
IB x
IB x+1
Figure 19-5 Address Space of Analog Input Modules with HART
Analog Output Modules with HART
Process image output table PIO per module:
QB x
QB x+1
QB x+2
QB x+3
Example: Output value channel 0: 61A8
QB x
QB x+1
Figure 19-6 Address Space of Analog Output Modules with HART
ET 200iS Distributed I/O Station
A5E00087831-02
Input value channel 0 (primary variable in S7 format)
Input value channel 1 (primary variable in S7 format)
H
61
H
Input value channel 0 = +25000 (primary variable)
A8
H
Output value channel 0 (primary variable in S7 format)
Output value channel 1 (primary variable in S7 format)
H
61
H
Output value channel 0 = +25000 (primary variable)
A8
H
Address Space of the Inputs and Outputs
19-3