Siemens SIMATIC ET 200iS Manual page 273

Distributed i/o station
Table of Contents

Advertisement

Electrical isolation
Between channels and backplane bus
Between the channels
Between channels and load voltage
(powerbus)
Between load voltage (powerbus) and
backplane bus
Permitted potential difference
between the inputs (U
Insulation tested with
Current consumption
from load voltage L+ (powerbus)
Power loss of the module
Measurement principle
Integration / conversion time / resolution
(per channel)
Integration time selectable
Interference frequency suppression in
Hz
Integration time in ms
Basic conversion time including
integration time (per channel) in ms
Additional conversion time for wire break
monitoring in ms
Resolution (incl. over-range)
Smoothing of measured values
Interference voltage suppression for f = n x
(f1 ± 1 %), (f1 = interference frequency)
Common-mode interference (U
V)
Normal-mode interference (peak value
of the interference < nominal value of
the input range)
Crosstalk between the inputs
Operational limits (in the entire temperature
range, relative to the input range)
ET 200iS Distributed I/O Station
A5E00087831-02
Voltages, Currents, Potentials
yes
yes, functional
yes
yes
)
DC 6,5 V; AC 30 V
CM
AC 500 V
typ. 70 mA
typ. 0.84 W
Analog Value Formation
integrating (Sigma-Delta)
yes
60; 50
66; 80
min. 66; min. 80
5
15 bits + sign
yes, selectable in 4 levels:
Level
none
weak
medium
strong
Interference Suppression, Error Limits
< 60
min. 90 dB
CM
min. 70 dB
min. -50 dB
± 1.5 K
Analog Electronics Modules
Time constant
1 x cycle time
4 x cycle time
32 x cycle time
64 x cycle time
14-59