Siemens SIMATIC ET 200iS Manual page 100

Distributed i/o station
Table of Contents

Advertisement

Wiring
Table 6-9
Connectable wire cross-sections for solid-
core cables
Connectable wire
cross-sections for
flexible cables
Number of wires per connection
Length of insulation to be stripped
Wire-end ferrules
complying with DIN
46228
Tightening torque
Danger
When connecting the wiring to the TM-PS, you must keep to degree of protection
IP 30. This is only possible if you keep to the values specified in the column Wiring
Rules for... TM-PS.
6.5.2
Wiring Terminal Module TM-E30S44-iS with Screw Terminals
Features
• When wiring terminal modules with screw terminals, the wires are secured in
the terminal by screwing down the terminal.
• Wire-end ferrules are not necessary.
Requirements
Keep to the wiring rules.
Required Tools
Screwdriver with 3 mm blade
6-16
Wiring Rules for the ET 200iS
Wiring Rules for...
Without wire-end
ferrule
With wire-end ferrule 0.5 to 2.5 mA
Without installation
collar
With insulation collar
0.25 to 1.5 mm
TM-PS
TM-E (spring and
screw terminals)
0.5 to 4 mA
0.14 to 2.5 mA
0.5 to 2.5 mA
0.14 to 2.5 mA
0.14 to 1.5 mA
1 wire
1 or combination of 2
wires up to 1.5mm
(total) in a common
wire-end ferrule
9 mm
Shape A, 8 to 9 mm
Shape A, up to 21
long
mm long
Shape E, 8 to 9 mm
Shape E, up to 12
long
mm long
0.5 - 0.7 Nm
ET 200iS Distributed I/O Station
A5E00087831-02

Advertisement

Table of Contents
loading