Analog Electronics Modules
Parameters of 2AO I
All parameters are set with SIMATIC PDM.
Table 14-87 Parameters of 2AO I
Parameters of 2AO I
Format of the analog
values *
Channel x ( x = 0, 1)
Output type
Output range
Response to CPU/ master
STOP
Substitute value
Group diagnostics
Wire break diagnostics
Short circuit diagnostics
* Entered automatically by SIMATIC PDM. See IM 151-2 parameters.
14-68
Range of Values
SIMATIC S7
SIMATIC S5
I (current)
deactivated
4 to 20 mA
0 to 20 mA
Output no current/voltage
Apply substitute value
Hold last value
Every value of the nominal
range
enabled
disabled
enabled
disabled
enabled
disabled
Default
SIMATIC S7
ET 200iS
I (current)
Channel
4 to 20 mA
Channel
Output no
Channel
current/voltage
4.0000 mA
Channel
enabled
Channel
enabled
Channel
enabled
Channel
ET 200iS Distributed I/O Station
Effective for
A5E00087831-02

Advertisement

Table of Contents
loading

Table of Contents