PROFIBUS DPV1
The ET 200iS meet the requirements of DPV1. Naturally, the DP master must also
meet the requirements of DPV1 (refer to the documentation of the DP master).
The following table shows the new functions of PROFIBUS DPV1 slaves compared
with an S7 DP and PROFIBUS DPV0 slave:
Table 7-1
Comparison of DPV1, S7 DP and DPV0
Function
Parameter assignment and configuration with
GSD file
Parameter assignment and configuration with
HW Config
Cyclic data exchange
Acyclic data exchange
(read/write data record):
•
Free access to parameters
on the field device
•
Reassignment of
parameters of the
application process
Diagnostics
•
ID-Related diagnostics
•
Module status
•
Channel-related diagnostics
Interrupts
•
Diagnostic interrupt
•
Hardware interrupt
•
Remove/insert interrupt
•
Update interrupt
•
Time stamp
* in DPV1, interrupts are also reported with the CPU in the RUN mode. Exception If you operate the ET 200iS with an
S7-400, the interrupts are only reported when the CPU is in the STOP mode.
ET 200iS Distributed I/O Station
A5E00087831-02
DPV0
S7 DP
Slave
X
---
x
x
X
X
Class 1
---
X
services
(parameter
assignment
master, e.g.
PLC)
Class 2
X
X
services (e.g.
PG/OP)
X
X
X
---
X
---
---
X
---
X
---
X
---
---
---
X
Commissioning and Diagnostics
DPV1
Slave
Slave
---
x
X
X
X
One interrupt can be
reported per diagnostic
X
frame. In DPV1 and S7
X
DP, an interrupt consists
of a slave diagnostic
X
message that is
accompanied by an
X*
acknowledgment
mechanism that does not
X*
exist in DPV0.
X*
X*
X
Note
7-3