Appendix D
PROFIBUS-PA Status Byte
D.1

Overview

This appendix describes the status byte reported by the transmitter to a PROFIBUS host. The output
of each AI, AO, and totalizer function block is a 5-byte package: four bytes of process information
and one byte indicating measurement quality, also called the status byte. The format of the status byte
depends on whether the transmitter is configured for classic mode or condensed mode.
D.2

Classic-mode status byte format

Tables D-1 through D-6 describes the format of the status byte when the transmitter is configured for
classic mode. Refer to Section 3.7.3.6 of the PROFIBUS-PA Profile for Process Control Devices
v3.01 for more information.
Table D-1
Classic-mode status byte format
Status
bits
Meaning
00
Bad
01
Uncertain
10
Good – Non-cascade
11
Good – Cascade
Table D-2
Sub-status format – Bad status
Bits
Meaning
0011
Device failure
0100
Sensor failure
0111
Out of service
Configuration and Use Manual
Comment
The measurement is not useful.
The quality of the measurement is below
normal, but may still be useful.
The quality of the measurement is good, but
alarms may be indicated by the sub-status.
The measurement is good.
Comment
TRUE if the following alarm codes are active:
A001, A002, A014, A029, or A030.
TRUE if the following alarm codes are active:
A003, A004, A005, A016, or A017.
See the profile specification for details.
137