MCO 305 Operating Instructions

Commissioning Guide

This guideline is only describing basic configuration and optimizing of MCO 305, before starting the following
steps must be completed:
1. Basic commissioning of FC 300. NOTE: FC 300 must be optimized and have good control over the motor
and application before commissioning MCO 305! Guidelines can be found in FC 300 Operating
Instructions (MG.33.AX.XX).
2. Install the PC software tools (MCT 10 and APOSS)
3. Establish communication between PC and FC 300 using USB, RS485 or PROFIBUS DPV1.
Then follow these steps to set-up and optimize MCO 305:
1. Setting of basic MCO 305 parameters (groups 32-** and 33-**).
2. Connect and test encoder(s).
3. Optimize PID controller.
NB!:
Error 113 will show up right after power up if the FC 300 is not ready. The FC 300 is in the "Not
ready" state when:
it has an alarm (trip),
it is in hand mode, [Hand on] key,
local LCP stop is activated, [OFF] key,
there is no signal on input 37 safe stop (only FC 302).
Error 113 can only be reset using the ERRCLR command or with BREAK [Esc] in the PC software and only
when the FC 300 is in the "ready" state, which means none of the above may be true.
The FC 300 monitoring function can be switched off by selecting [0] in par. 33-82 Drive Status Monitoring.
Read the Safety Instructions before installing the drive.

Basic MCO Parameter Settings

The following parameters must always be checked and if necessary adjusted. Depending on the require-
ments of the application it might be necessary to adjust other parameters as well.
For the other parameters you can use the default settings at first and then optimize the controller as
needed at a later point in time with a Testrun.
The MCT 10 Set-up Software Tool will support you to set the parameters in Local Control Panel LCP.
For a detailed description of all parameters and there options please refer to the chapter Parameter
Reference.
Once the parameter settings are complete, it is recommended to save the settings.