Danfoss MCO 305 Operating Instructions Manual page 38

Hide thumbs Also See for MCO 305:
Table of Contents

Advertisement

MCO 305 Operating Instructions
1) Selected in parameter 5-00 Digital I/O mode.
The digital inputs are galvanic isolated from the internal electronics and can be sourced
by an external 24V power supply.
Digital outputs
Number of programmable digital outputs .........................................................................8 (6)
Terminal block ................................................................................................................ X59
Terminal number ................................................................................... 1
Driver type .............................................................................................................. Push/Pull
Logic ................................................................................................................ PNP or NPN
Voltage level ....................................................................................................... 0 - 24 V DC
Max. output current (sink or source) with internal power supply (total ) ..............................40 mA
Max. output current (sink or source) with external power supply (per output) ..................... 100 mA
1) Terminals X59-1 and X59-2 can be programmed as input, parameter 33-60.
2) Selected in parameter 5-00 Digital I/O mode.
Combined digital inputs/outputs
Number of digital outputs which can be used as digital inputs ................................................. 2
Terminal block ................................................................................................................ X59
Terminal number ............................................................................................................. 1, 2
Logic ................................................................................................................ PNP or NPN
Voltage level ....................................................................................................... 0 - 24 V DC
Voltage level, logic.0. PNP ....................................................................................... < 10 V DC
Voltage level, logic.1. PNP ....................................................................................... > 17 V DC
Voltage level, logic.0. NPN ...................................................................................... > 13 V DC
Voltage level, logic.1. NPN ........................................................................................ < 6 V DC
Maximum voltage on input ......................................................................................... 28 V DC
1) Terminals X59-1 and X59-2 can be programmed as input, parameter 33-60.
2) Selected in parameter 5-00 Digital I/O mode.
24 V DC supply output
Terminal block ................................................................................................................ X58
Terminal number ............................................................................................................. 1, 2
Maximum load .............................................................................................................65 mA
The internal 24V power supply can be disconnected via parameter 33-85, an external
24V power supply must then be connected to X58-1 and X58-2.
Encoder inputs
General specifications:
Number of encoder inputs .................................................................................................... 2
Terminal block .................................................................................................... X55 and X56
Terminal number .................................................................................. 5, 6, 7, 8, 9, 10, 11, 12
Input impedance .......................................................................................................... 120
Maximum voltage on inputs .......................................................................................... 5 V DC
Cable type .......................... Screened cable with a twisted pair of wires for each encoder channel
Incremental encoder specifications
Incremental encoder type ........................................................................................RS422/TTL
Maximum frequency .................................................................................................. 410 kHz
Phase displacement between A and B.......................................................................... 90˚± 30˚
Maximum cable length ................................................................................................300m
38
__ General Specifications __
MG.33.K2.02 – VLT is a registered Danfoss trademark
1)
1)
1)
, 2
, 3, 4, 5, 6, 7, 8
2)
1)
2)
1)
2)

Advertisement