■Details on input area
Global variable
DN00_STA_IN[0]
AL
DN00_STA_IN[1]
WR
DN00_STA_IN[2]
FWR
DN00_STA_IN[3]
RVR
DN00_STA_IN[4]
IRDY
DN00_STA_IN[5]
CFN
DN00_STA_IN[6]
RFN
DN00_STA_IN[7]
FA1
DN00_STA_IN[8]
to
Drive Status
DN00_STA_IN[15]
Rotation Speed
DN00_DATA_IN
Monitor
Name
Alarm
0:Normal
output
1: Fault/Trip
0:Normal
Warning
1:Warning
During
0:During reverse run/Stopping
forward
1: During forward run
operation
During
0:During forward run/Stopping
reverse
1:During reverse run
operation
Operation
0:Not ready
ready
1:Ready
Ctrl. from
0:Follow the setting of parameter A002.
Net
1:DeviceNet reference
Ref. from
0:Follow the setting of parameter A001.
Net
1:DeviceNet reference
Constant
0:Accelerating or decelerating/Stopping
speed
1:Frequency agree
reached
DN00_STA_IN [15] to [11]
1: Startup
2: Not ready
3: Ready
4: Operation in
progress
5: Stopping
6: Fault/Trip stop
7: Fault/Trip
If parameter P049 (Number of Poles for Rotation Speed
Setting) is set appropriately, the rotational speed unit is
-1
[min
].
If parameter P049 (Number of Poles for Rotation Speed
Setting) is set to 0, the frequency is monitored in units of
[0.01 Hz].
6. DeviceNet Settings
Description
[10]
[9]
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
[8]
1
0
1
0
1
0
1
10