Module Description and Accessories
Digital outputs
Number of outputs
Galvanic isolation
in groups of
Supply voltage Vp
Rating
Ripple
Permissible range (including ripple)
Output current for "1" signal
Short-circuit protection
Voltage induced on circuit interruption
limited to
Switching frequency
resistive load (24 V/50 mA)
(max. 8.5 W)
inductive load (time constant max. 50 ms)
lamp load (max. 5 W)
Simultaneity factor at 55 °C
(Number of outputs simultaneously
energized)
Residual current at "0" signal
Output voltage at "1" signal
Max. length of
shielded twisted-pair cable
Rated insulation voltage to VDE 0160
Insulation group
tested at
M
int
5V
Position
decoding,
counting,
positio-
ning
Shield potential
2-6
4n7
Fig. 2-3. Block Diagram of the Output Circuit
4 (2 per channel)
yes
1
24 V DC
3.6 V max.
20 to 30 V
0.5 A max.
Fuse, 0.8 A fast
- 23 V
200 Hz max.
2 Hz max.
8 Hz max.
100 %
1 mA max.
Vp - 3 V min.
1000 m (3300 ft)
30 V DC
C
500 V AC
D+
D -
IP 240
+Up
+Up
24 V
EWA 4NEB 811 6120-02a