IP 240
FB 38
NETWORK 1
0000
FB38 SAVES FLAG WORDS 200 TO 254 IN A SPECIFIED DATA BLOCK.
THE DATA BLOCK MUST HAVE A LENGTH OF AT LEAST 30 DATA WORDS
(DW0 - DW29).
NAME :FLAG.SAV
ID
:DBNR
I/Q/D/B/T/C: B
0008
:B
=DBNR
0009
:***
NETWORK 2
000A
000A
:L
KF +200
000C
:T
DW
29
000D
:L
KF +0
000F
:T
DW
28
0010 M001 :DO
DW
29
0011
:L
MW
0
0012
:DO
DW
28
0013
:T
DW
0
0014
:L
DW
29
0015
:ADD KF+2
0017
:T
DW
29
0018
:L
DW
28
0019
:ADD KF+1
001B
:T
DW
28
001C
:L
KF +254
001E
:L
DW
29
001F
:>=F
0020
:JC
=M001
0021
:BE
EWA 4NEB 811 6120-02a
SAVE FLAGS
PRESET THE POINTERS
(DW28 AND DW29)
INCREMENT THE POINTERS
FLAG WORD POINTER
DATA WORD POINTER
FLAG WORDS 200 TO 254 SAVED
IN THE DATA BLOCK ?
Position Decoding
LEN=39