Siemens Simatic S5 IP 240 Manual page 150

Counter/positioning/position decoder module
Hide thumbs Also See for Simatic S5 IP 240:
Table of Contents

Advertisement

IP 240
FB 40
NETWORK 1
0000
CHANNEL 1 OF THE IP 240 IS CONFIGURED IN COUNTING MODE.
DIGITAL OUTPUT 1 AND THE INTERNAL GATE CONTROL ARE ENABLED.
THE CONTROL BITS ARE ALSO INITIALIZED AND TRANSFERRED.
NAME :CONFIG
0005
:JU FB 171
0006 NAME :STRU.DOS
0007 BGAD :
KF +128
0008 KANR :
KF +1
0009 DBNR :
KF +14
000A DIG
:
KH 0001
000B PRA
:
KH 0000
000C EXT
:
KH 0000
000D PAFE :
FY
8
000E BER
:
KF +0
000F ABIT :
KY 1,0
0010
:
0011
:
0012
:L
KB 0
0013
:L
FY
8
0014
:><F
0015
:S
F
11.0
0016
:
0017
:A
F
10.0
0018
:R
F
10.0
0019
:BE
FY
8
= AUX BYTE
F
11.0 = GROUPPAFE
F
10.0 = FILL ACTIV
EWA 4NEB 811 6120-02a
CONFIGURING THE IP240 CHANNEL 1
-AUX BYTE
-AUX BYTE
-GROUPPAFE
-FILL ACTIV
-FILL ACTIV
SCRATCH FLAG BYTE IN THE IP 240 PROGRAM
GROUP SIGNAL FROM ALL FB171/172
AUX. FLAG: PROPORTIONING STARTED
LEN=31
MODULE ADDRESS OF THE IP 240
CHANNEL NUMBER
DATA BLOCK 14 => CHANNEL 1
ENABLE THE DIGITAL OUTPUT
NO PROCESS INTERRUPTS
INTERNAL GATE CONTROL
ERROR BYTE
I/O AND E I/O AREA (NOT FOR 115U)
SYSTEM DATA RS0 IS NOT
AFFECTED WHEN
FB172/FCT3 IS INVOKED (ONLY FOR 150U)
SCAN FOR ERROR FLAG
GROUP SIGNAL FOR PAFE
RESET AUXILIARY FLAGS
Counting
8-25

Advertisement

Table of Contents
loading

Table of Contents