Table A.2 UPS Alarm and Warning Messages (continued)
Alarm/Warning
Description
Battery mode
The UPS is operating on battery power
Battery
The battery temperature has exceeded the
overtemp
threshold setting
Battery
The battery polarity is reversed
reversed
Battery series
The battery detected does not match the setting
not qualified
parameter
Battery test
The battery capacity dropped below the threshold
failed
for the battery test
Battery test
The battery test has been started either by
started
automatic or manual initiation
Battery test
The battery test has been stopped either by
stopped
completion or manual initiation
Battery to utility
The load is powered by bypass (utility) power due to
transition
depletion of battery power or battery failure
Battery voltage
The battery voltage is outside of normal operating
abnormal
parameters
Bypass
The bypass input voltage or frequency exceeds
abnormal
normal operating range
Bypass
The bypass input voltage or frequency exceeds
abnormal in
normal operating range; the UPS is operating in
ECO mode
online or battery mode
Bypass back-
A bypass short circuit has been detected while in
feed
battery mode
This alarm will be generated if in the settings menu, if
Bypass disabled
the output frequency is set to Auto, BypDisa or 50
Hz, BypDisa or 60 Hz, BypDisa
Bypass mode
The UPS is operating on bypass power
Bypass over
The connected equipment has exceeded the bypass
current
ratings. 
Bypass phase
The AC bypass input phase rotation is reversed in a
reversed
single module system system.
The charger output voltage is abnormal and the
Charger fault
charger has been turned off
Communication
An internal communication problem has been
fail
detected
DC bus
A DC bus fault has occurred and the load will transfer
abnormal
to bypass power if available
58
Action
Check the upstream input breaker(s) to ensure they are
closed
Verify the ventilation openings are not block or Contact
Vertiv Technical Support
Call a qualified electrician to verify the battery wiring or
Contact Vertiv Technical Support
Call a qualified electrician to verify the battery wiring or
Contact Vertiv Technical Support
Replace battery
None required
None required
Check the upstream input breaker(s) to ensure they are
closed and wait for input power to return or Contact Vertiv
Technical Support
Contact VertivTechnical Support
Check the upstream bypass input breaker(s) to ensure
they are closed
Check the upstream bypass input breaker(s) to ensure
they are closed
Contact Vertiv Technical Support
None required or change setting to Auto, BypEna
Check UPS display for other alarms or Contact Vertiv
Technical Support
Verify the connected load and disconnect any
unauthorized equipment or check if load is properly
balanced
Call a qualified electrician to verify the input phase rotation
or Contact Vertiv Technical Support
Contact VertivTechnical Support
Contact VertivTechnical Support
Contact VertivTechnical Support
Vertiv | Liebert® EXS™ Installer/User Guide