Table 3.5 Settings Available at the Display Panel
Tab
Settings
Auto restart
Auto restart delay
Guaranteed Shutdown
Remote Control
System
Remote Power ON delay
Remote Shutdown delay
IT Earthing System
Dry Contact3 Input
Dry Contact4 Input
Voltage Selection
Startup On Bypass
Frequency Selection
Inverter Sync Range
Bypass Voltage Upper Limit
Bypass Voltage Lower Limit
Output
Bypass Frequency Range
Run Mode
ECO Voltage Range
NOTE: ECO options appear
only when in ECO mode
ECO Frequency Range
ECO Requalification Time
38
Parameter range
Disable, Enable
0 - 999 seconds
Disable, Enable
Disable, Enable
0 - 999 seconds
0 - 999 seconds
Disable, Enable
Maintain mode, Any mode shutdown, Battery mode shutdown
Maintain mode, Any mode shutdown, Battery mode shutdown
208/120V, 220/127V
Disable, Enable
Auto w/ Bypass Enable, Auto w/ Bypass Disable,
50Hz w/ Bypass Disable, 60Hz w/ Bypass Disable
±0.5Hz, ±1.0Hz, ±2.0Hz, ±3.0Hz, ±4.0Hz, ±5.0Hz,
+10%
-10%, -15%, -20%
±5.0Hz, ±10.0Hz
Normal, ECO Mode
±10%
±1.0Hz, ±2.0Hz, ±3.0Hz
5, 15, 30 minutes
Default setting
Enable
10
Disable
Enable
0
0
Disable
Maintain mode
Maintain mode
208/120V
Disable
Auto w/ Bypass Enable
±3.0Hz
+10%
-10%
±10.0Hz
Normal
±10%
±3.0Hz
5
Vertiv | Liebert® EXS™ Installer/User Guide