Liebert EXL UNINTERRUPTIBLE POWER SUPPLY USER MANUAL 10H52226UM60 - rev. 1...
Page 3
Delivery subject to availability. Right of technical modifications is reserved. Liebert EXL S1 may differ from the model displayed on the front cover. User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Liebert EXL S1 Introduction 1. INTRODUCTION This User’s Manual contains information on the installation, operation and use of the Liebert EXL S1 Uninterruptible Power System (UPS). We recommend reading this document before installing the equipment, which must be operated only by qualified personnel.
Introduction Liebert EXL S1 1.3. Terms used 1.3.1. Service Bypass A switch that provides continuous supply to the load via the bypass input power line during maintenance work; also referred to as the maintenance bypass. 1.3.2. Static Bypass Switch A thyristor switch which connects the load directly to the power line; also referred to as a static switch or static bypass.
(built to IP20, with optional filters available for special conditions). However, it is not possible for Vertiv to ensure that foreign bodies will not be introduced during on-site installation, or when the UPS doors & covers are "open" and the electrical terminals are exposed to allow power line connections to be made by the electrical contractor/installer.
Page 11
UPS module via its forced air-flow. Vertiv will not accept liability or pay damages deriving from accidents caused by the introduction of conductive foreign bodies into the UPS module or associated auxiliary equipment/components, which occurred before or after the unit is placed into service in its operating environment.
Liebert EXL S1 Preparation For Use 2. PREPARATION FOR USE 2.1. Transport The equipment must be kept upright at all times and handled with care. Damage may be caused if it is dropped or subjected to severe impact. When moving the equipment with a forklift, secure it against tilting.
Page 13
Preparation For Use Liebert EXL S1 1757). Do not remove the retaining brackets which secure the UPS to the pallet because they are used to fasten the UPS to the floor. Wrench 17 mm Figure 1 - Remove these screws in both the sides Figure 2 - User Manual 10H52226UM60 - Rev.
2.4. Liebert EXL S1 1000/1200kVA cabinets assembly procedure (in case of cabinets shipped separated) The Liebert EXL S1 1000/1200kVA is composed by two cabinets, one contains the modules and one contains the switches, and they must be assembled and connected together as first step of the installation following the below procedure.
Page 15
Preparation For Use Liebert EXL S1 In the modules cabinet, remove the two lexan particulars and the iron one indicated below in red. User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 16
Liebert EXL S1 Preparation For Use Assemble the iron particulars in red as indicated by the arrows using supplied hexagonal head screws M6x30 + grower + washer. User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 17
Preparation For Use Liebert EXL S1 Connect the busbars of modules cabinet to the switches terminals in red as indicated by the arrows using supplied hexagonal head screws M12x35 + grower + washer. For a correct connection and installation of the busbars use contact grease.
Page 18
Liebert EXL S1 Preparation For Use Connect the signal wiring to the switches auxiliary contacts QS1,QS2 and QS4 (pin COM and pin N.O.), as indicated in the functional schematic. Reassemble the two lexan particulars and the iron one previously removed in the modules cabinet;...
Preparation For Use Liebert EXL S1 2.5. Environmental conditions The UPS must be installed vertically, on a level and even surface, and in an area protected from extremes of temperature, water and humidity. Do not stack the units or place objects on top of them.
Liebert EXL S1 Preparation For Use 2.6. Access to service area and cooling system When installed, the UPS can only be accessed from the front. All front doors have a maximum aperture of 90°. The area must have sufficient space for installation procedures to be carried out. Access doors must be wide enough to permit unobstructed transport of the device (chap.
Preparation For Use Liebert EXL S1 2.7. Installation and footprint The overall external dimensions of the UPS are listed on the final data table There are no restrictions on where you can position the UPS. The rear of the machine can be positioned against a wall.
Page 22
Preparation For Use Liebert EXL S1 FRONT CABLE ENTRY AREA Figure - Liebert EXL S1 300/400kVA - bottom view (gland plate) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 23
Liebert EXL S1 Preparation For Use FRONT Figure - Liebert EXL S1 300/400kVA bottom view (footprint and floor mounting holes) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 24
Preparation For Use Liebert EXL S1 FRONT Figure - Liebert EXL S1 300/400kVA - upper view (door open) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 25
Liebert EXL S1 Preparation For Use FRONT CABLE ENTRY AREA Figure - Liebert EXL S1 500kVA - bottom view (gland plate) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 26
Preparation For Use Liebert EXL S1 FRONT Figure - Liebert EXL S1 500kVA bottom view (footprint and floor mounting holes) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 27
Liebert EXL S1 Preparation For Use FRONT FRONT Figure 1 - Liebert EXL S1 500kVA - upper view (doors open) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 28
Preparation For Use Liebert EXL S1 FRONT Figure - Liebert EXL S1 600/800kVA bottom view (gland plate) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 29
Liebert EXL S1 Preparation For Use FRONT Figure - Liebert EXL S1 600/800kVA bottom view (footprint and floor mounting holes) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 30
Preparation For Use Liebert EXL S1 FRONT Figure - Liebert EXL S1 600/800kVA upper view (gland plate) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 31
Liebert EXL S1 Preparation For Use FRONT Figure - Liebert EXL S1 600/800kVA upper view (doors open) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 32
Preparation For Use Liebert EXL S1 FRONT Figure - Liebert EXL S1 1000/1200kVA bottom view (gland plate) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 33
Liebert EXL S1 Preparation For Use FRONT Figure - Liebert EXL S1 1000/1200kVA bottom view (footprint and floor mounting holes) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 34
Preparation For Use Liebert EXL S1 FRONT Figure - Liebert EXL S1 1000/1200kVA upper view (gland plate) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 35
Liebert EXL S1 Preparation For Use FRONT Figure - Liebert EXL S1 1000/1200kVA upper view (doors open) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 36
Preparation For Use Liebert EXL S1 BLANK PAGE User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Liebert EXL S1 Installation 3. INSTALLATION 3.1. Electrical preparations Warning For reasons of safety, the secondary access panel MUST NOT BE REMOVED. If, for any reason, it is necessary to remove this panel, the entire installation must be switched off and de-energized; otherwise complete safety cannot be guaranteed.
Installation Liebert EXL S1 3.2. Currents and suggested cable sizes For external wiring requirements refer to the local regulations for the selection of the proper conductors sizes. See Table 1 on page for the max currents and max cable sizes usable in the UPS.
Page 39
Liebert EXL S1 Installation Table 1: Currents and maximum cable sizes UPS devices (kVA) 1000 1200 Primary Power line 1250 1575 1880 1) 2) Max. current (A) Max. number of conductors connectable to BUS-BAR & cross section (mm 2x240 2x240...
Installation Liebert EXL S1 3.4. External protection devices This device is equipped with manual switches intended only for Service Bypass and Internal Service operations. It is therefore essential that the customer install external protection devices at the installation site. These must be installed near the unit and labelled as the line power separation device for the UPS (see IEC/EN 62040-1+A1:2013).
Liebert EXL S1 Installation 3.4.2. Primary line power input These should be capable of protecting the primary AC line power ahead of the UPS. It should be able to handle the maximum input current of the UPS (Table 1 on page ) and to interrupt the circuit at its maximum current level during a short circuit.
Installation Liebert EXL S1 Bypass Line Power Supply External Protection Backfeed Protection Disconnector FUSE To loads Figure - External protection devices 3.6. External electrical connections To access the external electrical connections, open the front door of the UPS and remove the secondary access panel (see Fig.
Liebert EXL S1 Installation 3.7. Power connections The power connections (see Fig. -Fig. ) on the front of the UPS are: • U, V, W - LINE POWER INPUT • U1, V1, W1 - LINE POWER BYPASS (only at the standard UPS type) •...
Page 49
Liebert EXL S1 Installation D- C+ Figure - Liebert EXL S1 300/400 kVA Customer power connections (front view) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 50
Installation Liebert EXL S1 FRONT Figure - Liebert EXL S1 300/400 kVA Customer power connections (right side view) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 51
Liebert EXL S1 Installation FRONT Figure - Liebert EXL S1 300/400 kVA Customer power connections (right side view) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 52
Installation Liebert EXL S1 FRONT U V W Figure - Liebert EXL S1 300/400 kVA Customer power connections (right side view) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 53
Liebert EXL S1 Installation FRONT Figure - Liebert EXL S1 300/400 kVA Customer power connections (left side view) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 54
Installation Liebert EXL S1 Figure - Liebert EXL S1 500 kVA Customer power connections (front view) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 55
Liebert EXL S1 Installation FRONT Figure - Liebert EXL S1 500 kVA Customer power connections (right side view) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 56
Installation Liebert EXL S1 W, W1, W2 V, V1, V2 U, U1, V1 FRONT PE/N Figure - Liebert EXL S1 500 kVA Customer power connections (left side view) User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Liebert EXL S1 Installation 3.8. Connecting the batteries UPS are supplied without the battery switch. It is mandatory that the Customer provides an external battery protection device, ensuring that they are correctly rated. Auxiliary signal contacts shall be assigned to a programmable input of XP11, so that the status of the switch can be monitored during the normal operation.
Installation Liebert EXL S1 Notice The most common battery type used in UPS installations is the valve regulated battery. Valve regulated cells are not sealed. The amount of gas given off is less than for flooded cells, but when planning the battery installation, allowance must be made for adequate ventilation and heat dissipation.
Page 65
Liebert EXL S1 Installation For details about XP4 position, see Fig. Figure - External Battery Connections User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Installation Liebert EXL S1 3.10. Handling the batteries Warning Batteries are a potential source of danger due to their electrical charge and chemical composition. Therefore, observe the handling instructions provided by the battery manufacturer. These usually can be found in the material which is included in the shipment.
This interface is a 10/100 MBit autonegotiation full/half duplex Ethernet Interface for LAN communication with Vertiv service software. This allows the setup and implementation of UPS parameters such as Battery detail and performance of the UPS. The Interface is SELV - isolated from UPS primary circuits.
CONNECTIVITY PANELS Liebert EXL S1 4.2. Customer connectivity panel The customer connectivity panel is placed as shown in Fig. 4 SLOT 1 SLOT 2 XP11 XP10 XP12 XP31 XP19A XP19B Figure - Customer connectivity panel User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Page 69
Liebert EXL S1 CONNECTIVITY PANELS Liebert EXL S1 is equipped with the following interfaces: • XS3 - Slot for Connectivity Products • XS6 - Slot for LIFE modem • XP6 - Serial Interface for external LIFE • XP10 - EPO connector •...
This slot is the reserved interface for LIFE modem card. This card provides an independent external modem interface for communication with LIFE service station. Ask your local Vertiv dealer for more details on LIFE and its benefits for your UPS system.
PIN 5-6-7 RPO Status CONTACT Form C dry contact. 1A @24 Vdc Contact Vertiv technical support for different configuration The maximum cable diameter is 0.75 mm Warning The external Push-Button must be voltage free and isolated from all sources and GND.
UPS outputs in the event of a malfunction, without creating synchronization problems. Warning This interface and its function are for authorized Vertiv service technicians, only. Do not remove any connected cable from this interface or connect any cable to it.
The Interface is SELV-isolated from UPS primary circuits. Warning This interface and its function are for authorized Vertiv service technicians, only. Do not remove any connected cable from this interface or connect any cable to it. User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Liebert EXL S1 Normal and safe operation 5. NORMAL AND SAFE OPERATION 5.1. Function The uninterruptible power supply (UPS) is connected between line power and electrical load. It protects the load from line power interruptions and power failures. Warning To avoid overheating inside the UPS, do not operate the unit for extended periods with the rectifier running, the Inverter switched off and the Bypass switch open.
Normal and safe operation Liebert EXL S1 5.1.4. Communication The UPS offers several interfaces for communication with computers. Further information is included in chap. 4. on page 5.2. Special features 5.2.1. Safe and reliable operation • Real on-line functioning, i.e. complete de-coupling of the load from all abnormalities in line power •...
5.4. Maintenance Bypass Switch (not available for 600/800/1000/1200kVA) Liebert EXL S1 is equipped with a Maintenance Bypass Switch (QS3) that allows the user to perform maintenance on the UPS without interrupting the supply to the load. Transfer to and from Maintenance must be done in accordance with the procedures 3 and 4 described in para 5.7.
Normal and safe operation Liebert EXL S1 5.5. Operating modes The UPS has four different operating modes. These are described below. 5.5.1. On-line operation Normal UPS operating mode. The connected loads are supplied from line power via the Inverter. The batteries are charged as necessary.
Liebert EXL S1 Normal and safe operation 5.5.3. Bypass operation In this operating mode, the connected loads are supplied from line power via the Static Bypass Switch. The Static Bypass Switch is used to provide power to the loads. If an overload or short-circuit on UPS output occurs, the Static Bypass Switch is automatically activated to provide uninterrupted power to the loads.
Normal and safe operation Liebert EXL S1 5.6. Placement into service 5.6.1. Forming If the UPS devices have not been used for one year or more, the intermediate circuit capacitors must be reformed. If the UPS devices are placed into service within one year after delivery (check nameplate), this action is not necessary.
Liebert EXL S1 Normal and safe operation 5.7. UPS switching procedures The following procedures refer to para 5.3. on page Warning If static switch module and relative switches are not assembled, refer to MSS user manual. 5.7.1. Procedure 1: UPS TURN-ON PROCEDURE Starting with the UPS completely deenergized, this procedure explains how to switch on the UPS and set it to Normal Operating Mode.
Normal and safe operation Liebert EXL S1 5.7.3. Procedure 3: TRANSFER FROM NORMAL MODE TO MAINTENANCE BYPASS MODE Starting with the UPS in the Normal Mode, this procedure explains how to transfer the load to Maintenance Bypass and shut down the UPS.
Liebert EXL S1 Normal and safe operation 5.8. Inverter STOP/START procedures 5.8.1. Single UPS - Start Inverter UPS in Bypass mode: To start the inverter and transfer the load to the inverter touch ‘Inverter On’ on the touch screen. 5.8.2. Single UPS - Stop Inverter UPS in normal mode: To stop the inverter and transfer the load to the Bypass line touch ‘Inverter Off’...
Page 84
Normal and safe operation Liebert EXL S1 BLANK PAGE User Manual 10H52226UM60 - Rev. 1 - 01/2017...
6. MAINTENANCE 6.1. Maintenance intervals Vertiv recommends that regular maintenance checks be carried out on-site by an authorized customer service. The UPS informs the user when the normal service life of a fan has ended. A replacement fan is recommended.
PARALLEL CONFIGURATION 7. PARALLEL CONFIGURATION Up to 8 Liebert EXL S1 units can be connected in parallel to increase power capacity and thus to provide more secure power to the load (redundancy). The modules in parallel exchange information via a 37-wire shielded cable.
PARALLEL CONFIGURATION Liebert EXL S1 7.3. Communication between UPS blocks UPS units exchange information through the connector cable (37 pin connector). Fig. displays the loop circuit, which is electronically monitored. The communication cables are shielded and must be run separately and away from the power cables.
Liebert EXL S1 PARALLEL CONFIGURATION 7.4.2. Procedure 2: UPS TURN-OFF PROCEDURE Starting with each UPS in Normal Mode, this procedure explains how to switch off the UPS units. When this procedure is followed completely, the output voltage will be completely turned off and any load(s) connected to the UPS output will be shut down.
PARALLEL CONFIGURATION Liebert EXL S1 7.4.4. Procedure 4: TRANSFER FROM MAINTENANCE BYPASS MODE TO NORMAL MODE Starting with each UPS in Maintenance Bypass, this procedure explains how transfer the load to Normal Mode and start the UPS. On each UPS, perform the following procedure:...
Page 91
Liebert EXL S1 PARALLEL CONFIGURATION 1) For fuse ratings, see the chapter with technical data 2) Values are determined by the dimensions of the Service Bypass 3) Switch, fused switch or circuit breaker System Bypass 3) 2) Load 3) 1)
Page 92
PARALLEL CONFIGURATION Liebert EXL S1 1) For fuse ratings, see the chapter with technical data 2) Values are determined by the dimensions of the Service Bypass 3) Circuit breaker or fuse 4) External Service Bypass (Ext. SBS) - must be a switch, a fused switch or a circuit breaker...
Liebert EXL S1 Options 8. OPTIONS Some of the options listed in this section may modify the data on the standard technical data tables (see chap. 9. on page 1 ). It may not be possible to use certain options simultaneously on the same UPS.
Page 96
Options Liebert EXL S1 Installation Remove the lateral painted panel of UPS. Assemble TCE and UPS together using the loose supplied material with TCE, see below figures. The figures refer to the TCE on the left If necessary, fix the cables to the mounting using the base cable fixing. These materials are loose supplied.
Page 97
Liebert EXL S1 Options TCE 400mm This option permits power cables to be routed through the top of the UPS. It can be installed both on the right and the left of the UPS, but the despatched configuration includes the TCE on the left. The TCE weighs 75kg.
Page 98
Options Liebert EXL S1 Installation Only for TCE mounted on the right, remove the lateral galvanized panel and mount it on the opposite side of the TCE. For both the versions, remove the lateral painted panel of UPS. Assemble TCE and UPS together using the loose supplied material with TCE, see below figures.
Liebert EXL S1 Options If necessary, fix the cables to the mounting using the base cable fixing. These materials are loose supplied. The figure refers to the TCE on the left Mount the lateral painted panel previously removed on the side of TCE.
(the rating available are 400A, 800A, 1600A and 2500A). 8.9. Parallel kit - adapter (Liebert EXL S1 to legacy 80-NET) It is used for parallel connection between Liebert EXL S1 and 80-NET, because of different connectors installed. User Manual 10H52226UM60 - Rev. 1 - 01/2017...
UPS, see below figure. For the connection of the cables of the synch distribution, refer to the MSS manual. Warning This switch has to be operated by authorized Vertiv service technicians, only. User Manual 10H52226UM60 - Rev. 1 - 01/2017...
Liebert EXL S1 Technical data 9. TECHNICAL DATA 9.1. Liebert EXL S1 00-500kVA General conditions of technical data table: The data shown are typical and refer to 25°C ambient temperature and nominal input and output conditions, unless otherwise specified. Not all data shown apply simultaneously. Data apply to the standard version, unless otherwise specified.
Page 104
Technical data Liebert EXL S1 UPS model Liebert EXL S1 Power (kVA) Max. altitude above sea-level without derating (m) 1000 (for higher altitudes complies with IEC/EN 62040-3) Immunity to electrical interference IEC/EN 62040-2:2006 EMC CLASS IEC/EN 62040-2:2006 Class C3 Input...
Page 105
Liebert EXL S1 Technical data UPS model Liebert EXL S1 Power (kVA) 110% continuous 125% 10 min. Overload capacity 150% 1 min. Short circuit current for ≤200ms 2,2In 380/400/415 Nominal output voltage (V) Nominal output frequency (Hz) 50 (60 selectable) Voltage stability in steady state condition for input ±1...
Page 106
Technical data Liebert EXL S1 UPS model Liebert EXL S1 Power (kVA) Inverter to Bypass No Break (ms) Transfer time with inverter synchronous to Bypass Bypass to Inverter ≤2 (ms) Default transfer delay time (inverter to Bypass) with inverter not synchronized to Bypass (ms) For tolerances see IEC/EN 60146-1 or DIN VDE 0558.
Liebert EXL S1 Technical data 9.2. Liebert EXL S1 600-1200kVA General conditions of technical data table: The data shown are typical and refer to 25°C ambient temperature and nominal input and output conditions, unless otherwise specified. Not all data shown apply simultaneously. Data apply to the standard version, unless otherwise specified.
Page 108
Technical data Liebert EXL S1 UPS model Liebert EXL S1 Power (kVA) 1000 1200 EMC CLASS IEC/EN 62040-2:2006 Class C3 Input 380/400/415 Nominal voltage Input voltage range @ nominal load without battery discharge (V) to 460 Nominal frequency (Hz) 50 (60 selectable)
Page 109
Liebert EXL S1 Technical data UPS model Liebert EXL S1 Power (kVA) 1000 1200 Short circuit current for ≤200ms 2,2In 380/400/415 Nominal output voltage (V) Nominal output frequency (Hz) 50 (60 selectable) Voltage stability in steady state condition for input variations (AC &...
Page 110
Technical data Liebert EXL S1 The modules cabinet is 2100mm wide and the switches cabinet is 750mm wide. The sum of these two widths is greater than the width of the fully assembled unit, which is indicated in the table. This difference is due to the protrusion of some connecting bars and closures from the modules cabinet, which need to be assembled to the switches cabinet during the installation in field.