Page 1
Liebert® EXM UPS User Manual 20kVA to 100kVA, 208/120V, 50/60Hz...
Page 2
The products covered by this instruction manual are manufactured and/or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use or disclosure of it without the written permission of Vertiv is strictly prohibited.
Observez toutes les précautions de sécurité appropriées lorsque vous travaillez sur à proximité d’une source c.c. de sécurité appropriées dès que vous vous trouvez à proximité d’une source c.c. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Page 8
One person should never work alone, even if all power is disconnected from the equipment. A second person should be standing by to assist and to summon help in case of an accident. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Page 9
Notez également que les courants de fuite à la terre de la charge seront acheminés par ce dispositif DDFT. Cet équipement doit être mis à la terre conformément au code national de l'électricité. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Page 10
All operations described in this section must be performed by properly trained and qualified electricians ™ or technical personnel. If any difficulties are encountered, contact Vertiv . See the back page of this manual for contact information.
Page 11
Toutes les opérations décrites dans cette section ne doivent être effectuées que par des électriciens ou des techniciens professionnels dûment formés et qualifiés . En cas de difficultés, communiquez avec Vertiv ™ . Pour obtenir les renseignements de contact, consultez la dernière page de ce manuel.
AC output Requests the user to consult the manual Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 Recycle DC voltage AC voltage Equipment grounding conductor Bonded to ground Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
50 or 60Hz input and provide a matching output frequency conversion. When configured for scalability, the UPS’ capacity can be increased in 20 kVA increments. Based on the configuration, a power module can be set to a redundant operation mode. Contact Vertiv Services about adding ™...
™ Compare the contents of the shipment with the bill of lading. Report any missing items to the carrier and your local Vertiv representative immediately. Check the product label on the back of front door and confirm the contents match the UPS model, capacity and main parameters that were ordered.
Such failure may cause the unit to tip over, injuring personnel and damaging the equipment. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Leave a minimum of 24 in. (610mm) between the top of the UPS frame and the ceiling to permit adequate air ™ circulation above the unit. Vertiv recommends against using air conditioning or other systems that blow air onto the top of the unit.
(BDC/MBC must be on right side of the Liebert EXM) Bypass (Battery Cabinets must be on the left side of the ® Battery Battery Distribution Liebert EXM) Cabinet Cabinet Cabinet Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Liebert IntelliSlot Ready Switch Bays 1, 2, 3 ® The Static Bypass Assembly has three Liebert IntelliSlot interface card bays and connections for optional ancillary cabinets and for other options. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
• Battery cables - See the Liebert EXM External Battery Cabinet manual, SL-25651, for battery installation guidelines and instructions. The manual ships with the battery cabinet and is available at Vertiv’s Web site: www.vertiv.com NOTE Table 15 gives nominal currents for determining the size of UPS power cables. Other important factors to consider include cable route length and coordination with protective devices.
EXM Input as Single Source Dual-Input ® To wire the Liebert EXM as a single source dual-input UPS, remove factory-installed links between rectifier and bypass input busbar (see Figure 9). Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
2. Input and bypass must share the same single source. Field-Supplied Wiring 3. A neutral is required from the system AC input source. Vertiv recommends a full-capacity neutral conductor and grounding conductors. 4. Bypass and rectifier inputs and output cables must be run in separate conduits.
MBB - Maintenance Bypass Breaker 2. Input and bypass must share the same single source. MIB - Maintenance Isolation Breaker 3. A neutral is required from the system AC input source. Vertiv * External Overcurrent Protection recommends a full-capacity neutral conductor and grounding by others conductors.
3-Wire + GND Static Bypass * Rectifier AC Input 3-Wire + GND UPS Cabinet Battery The bypass distribution cabinet is available with a 480V, 600V or 208V optional internal transformer. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Detail A 3. Shown with seismic mounting bracket. 4. All wiring must be in accordance with national and local electrical codes. 78.56" (1994mm) DETAIL A FRONT VIEW Door Removed Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
The Alber BDSUi fuse block provides 208V nominal from the UPS output (L-L) and the fuse is rated at 8A. The ® Alber BDSUi power wiring is shown in SL-25651, the Liebert EXM Battery Cabinet manual. Figure 10 Accessory fuses Alber BDSUi Back-Feed Fuse Block Breaker Fuse (optional) Block Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
(LOW BATTERY) NOTE Shunt trips are required in upstream breakers to allow back-feed protection to function properly. Shunt trip of the upstream rectifier input breaker and bypass input breaker is required. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Toutes les opérations décrites dans cette section ne doivent être effectuées que par des électriciens ou des techniciens professionnels dûment formés et qualifiés. En cas de difficultés, communiquez avec ™ Vertiv . Pour obtenir les renseignements de contact, consultez la dernière page de ce manuel. NOTE Proper grounding significantly reduces problems caused by electromagnetic interference.
Figures 7 and 8 for details. System Output When using an external distribution panel for load distribution, the output neutral and input neutral must be separated at the input to the UPS. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
3.2.10 Cabling Procedure WARNING All operations described in this section must be performed by properly trained and qualified electricians ™ or technical personnel. If any difficulties are encountered, contact Vertiv . See the back page of this manual for contact information. AVERTISSEMENT Toutes les opérations décrites dans cette section ne doivent être effectuées que par des électriciens ou...
Low Battery COM Low Battery NC NOTE All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 80 and 200 feet (25-60m), respectively. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
BDC interface is on the Dry Contact Terminal Block at J26. Refer to Figure 15 for circuit details. For ® further information, refer to the Liebert EXM BDC manual, SL-25653, available at Vertiv’s Web site. NOTE All auxiliary cables of terminal must be double-insulated. Wire should be 20-16AWG stranded for maximum runs between 80 and 200 feet (25-60m), respectively.
® Liebert EXM’s internal circuitry and control boards. Exceeding 12V will also put the Liebert EXM in an EPO state, and the unit will not reset, making it non-functional. The UPS has an Emergency Power Off (EPO) function operated by a button on the control panel or by a remote contact provided by the user.
4. Unit bottom is structurally adequate for forklift handling. 5. Control wiring and power wiring must be run in separate conduits. 6. Vertiv recommends using only copper cables. 7. All wiring is to be in accordance with national and local electrical codes.
Control Filter Output oC Output oB Input bA Output oA Input bB Input bC Bypass Replaceable Module Air Filter Power Modules FRONT RIGHT SIDE Door Open Door Open Side Panel Removed Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
IS-UNITY-DP: This card can be used instead of the standard card if communication to two third-party platforms is required. Third-party platforms include SNMP and 485 (Modbus/BACnet) protocols. This card would still be used for communication ® between the Liebert EXM and Vertiv’s Trellis NMS and LIFE Services. All communication protocols are active simultaneously. ® • Liebert IntelliSlot Dry Contact Card (IS-RELAY): Provides dry contact alarm information, including: On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals for communication to a remote monitoring system.
Summary Alarm* Closed if Summary Alarm occurs Common - Summary Alarm* — On UPS Closed if On UPS (inverter) power On Bypass Closed if On Bypass Common - On Bypass — Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
UPS Fault Low Battery On Bypass Summary Alarm NOTE ® Refer to the Liebert IntelliSlot Relay Card manual, SL-23211, for additional details. the document is available at Vertiv’s Web site: www.vertiv.com Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Turning the UPS On and Off • Resetting faults • Enabling Energy Saving Mode Scan the QR code at right to obtain a copy of the Touchscreen Control Panel manual. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Risk of unauthorized changes to operational settings. Can cause equipment damage. The default PIN numbers should be changed immediately to prevent unauthorized personnel from changing UPS operation or even shutting down the UPS. Refer to the Touchscreen Control Panel, SL-26200, available at Vertiv’s Web site: www.vertiv.com...
Page 48
Module redundancy mode can be set at the factory or by the user. A maximum of one module can be set for redundancy. Availability of this feature depends on module capacity of the frame. Refer to the UPS control manual, SL-26200, for instructions on setting this feature. The manual is available at Vertiv’s Web site, www.vertiv.com Example 1 •...
Page 49
Vertiv Services. Power Conditioner Mode When EXM is set to Power Conditioner Mode, the battery is disabled in this mode. This mode can only be ™ enabled at the factory or by Vertiv Services. Maintenance Mode ® ® For maintenance or repair, the Liebert EXM may be operated in maintenance mode.
® ™ The Liebert EXM UPS can be set up for operation in Generator Mode by a Vertiv Services engineer. The setup requires connecting J26 Pin 2 to Pin 4. The battery charger is disabled in Generator Mode. UPS Startup ®...
This procedure must be performed by properly trained and qualified personnel who are knowledgeable about the operation of this system. Failure to follow these instructions will result in loss of power and possible damage to critical equipment. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Page 52
Même lorsque le système ASC est en mode de dérivation d’entretien et hors tension, des parties du ® système EXM de Liebert demeurent sous tension. L’entretien ne doit être confié qu’à un personnel qualifié et dûment formé. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
* External Overcurrent Protection By Others 2. Input and bypass must share the same single source. Field-Supplied Wiring 3. Vertiv recommends a grounding conductor. 4. Bypass and rectifier input and output cables EXM11011 must be run in separate conduits 5. Control wiring must be run in separate conduits.
The UPS system is now supplying power to the critical load. 10. Log in as Operator, Administrator or Service. 11. Touch the OPERATE tab. 12. Touch the Inverter On button. 13. To continue, confirm turning On the inverter when prompted. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Open the Rectifier Input Circuit Breaker and Bypass Input Breaker (if dual input). ™ If the MBC is a customer-issued switchgear or a non-Vertiv cabinet, open the breaker(s) that supply power to the UPS input and bypass input (if dual input).
2. Input and bypass must share the same single source. 3. A neutral is required form the system AC input source. EXM11002 Vertiv recommends installing a full capacity neutral conductor Rev. 3 and grounding conductors. 4. Bypass and rectifier inputs and output cables must be run in separate conduits.
EXM system that is being de-energized. ™ If the parallel switchgear is a matching Vertiv cabinet, open the Maintenance Isolation Circuit Breaker (MIB). Open all Module Output Breakers (MOB). Open the input breaker for each UPS and the breaker feeding the Maintenance Bypass Breaker (MBB) in the parallel switch gear.
™ • if “Auto Recovery after EOD Enabling” is enabled in the UPS configuration (set by factory or by Vertiv Services) • after the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes) ®...
3 to 60 minutes before end-of-discharge. 6.15.2 Battery End-of-Discharge (EOD) Protection If the battery voltage is lower than the end-of-discharge voltage, the battery converter will be shut down. Refer to Table 21. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Risk of power loss to connected load. Can cause damage to equipment. ® The load equipment is not protected from supply aberrations, such as spikes, sags and failures, when the Liebert EXM is operating in Load on Bypass Mode. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Dimensions, W x D x H, in (mm) 23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000) Weight, lb (kg) See Table 1 for weights Color RAL 7021 (Black) Protection Degree IEC (60529) IP20 Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
Vertiv ™ ou formé par Vertiv. Des hautes tensions c.a. et c.c. mortelles sont présentes dans cet équipement. Faites preuve d'une grande prudence lorsque vous travaillez à proximité d'un système ASC. Identifiez toujours la source d’un câble de raccordement avant de le débrancher. Identifiez les câbles déconnectés afin de pouvoir les reconnecter correctement.
Page 67
électrique avec le sol. En cas d'incendie associé à du matériel électrique, n'utilisez que des extincteurs à dioxyde de carbone ou homologués pour la lutte contre les incendies d'origine électrique. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...
10 years. The following components utilized in your UPS system have a limited life cycle and are specifically exempt from warranty. To prevent a wear-out failure of one of these components affecting your critical load operations, Vertiv ™...
A second log should be maintained for the battery module as directed by the battery manufacturer. Vertiv recommends a periodic walk-through inspection of the UPS and battery rooms to check for visible and ™...
Global Services. Reporting a Problem If a problem occurs within the UPS, review all alarm messages along with other pertinent data. This information should be given to the Vertiv ™ Services dispatcher. Call 800-543-2378 to report a problem or to request assistance.
Page 72
X - Means the content of the hazardous substances in at least one of the average quality materials of the part is outside the limits specified in SJ/T11363-2006 ™ Vertiv has been committed to the design and manufacturing of environment-friendly products. It will reduce and eventually eliminate the hazardous substances in the products through unremitting efforts in research.
Services at 800-543-2378 for assistance. ™ Soft Start Fail Rectifier could not start due to low DC bus voltage. Contact Vertiv Services at 800-543-2378 for assistance. This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is beyond the normal range.
Page 74
Contact Vertiv Services at 800-543-2378 for assistance. ™ Output Fuse Fail At least one of the output fuses is open. Contact Vertiv Services at 800-543-2378 for assistance. ™ Control Power 2 Fail Control Power 2 is abnormal or lost. Contact Vertiv Services at 800-543-2378 for assistance.
Page 75
Transfer Timeout The UPS will recover automatically and will transfer the load back to inverter power within an hour. ™ UPS working within a parallel system are not sharing load current correctly. Contact Vertiv Services at Load Sharing Fault 800-543-2378 for assistance.
Page 76
Environment in battery room needs attention. Rec Flash Update Rectifier firmware is being updated. Inv Flash Update Inverter firmware is being updated. Monitor Flash Update Monitor firmware is being updated. LBS abnormal LBS is abnormal. Vertiv™ | Liebert® EXM™ UPS 20-100kVA, 50/60Hz User Manual |...