The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
Page 4
7.10 Parallel Operations Determine Control Panel Firmware Version 7.11 Parallel Operations Control Panel Firmware Version 1.1 7.11.1 De-Energize a Vertiv™ Liebert® EXM Parallel System Control Panel Firmware Version 1.1 7.11.2 Reenergize a Liebert® EXM Parallel System Control Panel Firmware Version 1.1 7.12 Emergency Shutdown with EPO...
1 Important and Safety Instruction Save These Instruction This manual contains important instructions that should be followed during installation of the Vertiv™ Liebert® EXM. Read this manual thoroughly, paying special attention to the sections that apply to your installation, before working with the UPS.
Page 10
All operations described in this section must be performed by properly trained and qualified electricians or technical personnel. If any difficulties are encountered, contact Vertiv. See the back page of this manual for contact information.
2 Introduction The Vertiv™ Liebert® EXM UPS can be configured as either a fixed capacity or scalable, transformer free, online uninterruptible power system with 480 V input and 480 V output capability. The Liebert® EXM operates with a 60 Hz input.
Do not attempt to install the system if damage is apparent. If any damage is noted, file a damage claim with the shipping agency immediately and contact Vertiv Services at 800-543-2378 to inform them of the damage claim and the condition of the equipment.
Operating environment temperature of 74 °F-80 °F (23 °C-27 °C) for maximum battery life. 3.3.2 Environmental Considerations Before installing the Vertiv™ Liebert® EXM, verify that the UPS room satisfies the environmental conditions stipulated in Environmental Requirements on page 75 , paying particular attention to the ambient temperature and air exchange system.
WARNING! Risk of moving heavy unit. Can cause property damage, injury and death. Ensure that any equipment that will be used to move the Vertiv™ Liebert® EXM has sufficient lifting capacity. The Liebert® EXM's weight ranges from 748 to 1244 Ib (339 to 564 kg). See Table 8.3 on page 76...
3.5.3 Floor Installation If the Vertiv™ Liebert® EXM is to be placed on a raised floor, the UPS should be mounted on a pedestal that will support the equipment point loading. Refer to the bottom view in Figure 3.1 on the previous page to design this pedestal.
UPS. Liebert® bypass cabinets are designed to be bolted to the right side of the UPS (see Figure 3.5 on the next page ). Refer to Vertiv™ Liebert®...
Page 22
Description Vertiv™ Liebert® EXM connected only to the Vertiv™ Liebert® MBC. (The Liebert® MBC must be on right side of the Liebert® EXM). Liebert® EXM connected to the Battery Cabinets. (The Battery Cabinets must be on the left side of the Liebert® EXM).
Figure 3.7 Static Bypass Assembly Connections Item Description DB15 Ready switch Vertiv™ Liebert® IntelliSlot™ Bays 1, 2, 3 NOTE: See Figure 4.11 on page 34 Figure 4.14 on page 39 for details. The Control Module has three Liebert® IntelliSlot™ interface card bays and connections for optional ancillary cabinets and for other options.
WARNING! Risk of electrical shock. Can cause property damage, injury and death. Before connecting input power to the Vertiv™ Liebert® EXM. ensure that you are aware of the location and operation of the overcurrent protection devices that connect the UPS input/bypass supply to the power distribution panel.
A shunt trip coil of 480 V must be installed in the bypass input breaker if the system does not include a Vertiv™ Liebert® Bypass Cabinet. Refer to Figure 4.1 on the facing page for more details.
UPS (see Table 8.9 on page 77 ). 4.2.3 UPS Input Configuration By default, the Vertiv™ Liebert® EXM ships with internal links installed between the bypass input and main (rectifier) input (single input configuration).
The rectifier input, bypass, output and battery are easily accessible from the front of the unit for installation. All require lug type terminations. They are connected to busbars on the front of the Vertiv™ Liebert® EXM, as shown in Figure 4.3 on the next page .
Page 30
Vertiv™ Liebert® EXM UPS User Manual Figure 4.3 Input, Output and Battery Busbars Vertiv™ Liebert® EXM 50-200 kVA Frame Item Description Item Description Rec A Byp A Batt + Out B Rec B Byp B Bat - Out C Rec C...
Page 33
Figure 4.7 on the next page shows the back feed breaker wiring, located on the bypass static switch assembly. The Vertiv™ Liebert® EXM does not include internal back feed protection. A shunt trip coil of 480 V must be installed in the bypass input breaker and rectifier input breaker if the system does not include a Liebert®...
Page 35
NOTE: The ground busbar is easily accessible when the I/O panel is removed. Cable connections should be made before a cabinet is attached to the right side of the Vertiv™ Liebert® EXM or before the UPS is placed where another obstruction, such as a wall, is against the Liebert®...
Fuses The Vertiv™ Liebert® EXM’s main input and bypass input busbars are equipped with fuses (six locations; see Figure 5.2 on page 46 ). The type is Bussman, rated 450 A for 50-200 kVA units (170M4463 for main input and 170M4465 for bypass input) and rated 550 A for 250 kVA units.
NOTE: All auxiliary cables must be double insulated and shielded. Wire should be 20-16 AWG stranded for maximum runs between 80 and 200 ft (25-60 m), respectively. NOTE: Refer to SL-26103, the Vertiv™ Liebert® EXM Maintenance Bypass Cabinet manual for the Liebert® MBC wiring. 4.4.4 Battery Cabinet Interface Connectors The battery cabinet interface is on the Dry Contact Terminal Block at J22.
Do not apply more than 12 V to the Emergency Power Off (EPO) input. Exceeding 12 V on this input can damage the Vertiv™ Liebert® EXM’s internal circuitry and control boards. Exceeding 12 V will also put the Liebert® EXM in an EPO state, and the unit will not reset, making it non-functional.
Vertiv™ Liebert® EXM UPS User Manual 5 Installation Drawings The diagrams in this section illustrate the key mechanical and electrical characteristics of the Vertiv™ Liebert® EXM UPS system cabinets (UPS, Vertiv™ Liebert® MBC and battery). Figure 5.1 UPS Dimensions-Front View Notes to Figure Dimensions are in in.
Page 52
Vertiv™ Liebert® EXM UPS User Manual 4. 50-200 kVA Models: Bottom cable entry is available through removable access plates. Remove, punch to suit conduit size and replace. Top cable entry available through matching Vertiv™ Liebert® MBC or optional wiring cabinet.
6 Option Installation 6.1 Vertiv™ Liebert® IntelliSlot™ Communication The Vertiv™ Liebert® EXM has three Liebert® IntelliSlot™ ports to allow field installation of optional communication cards. Liebert® IntelliSlot™ cards communicate via Vertiv’s proprietary Velocity protocol to cards that translate the information into such protocols as SNMP and Modbus.
Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals for communication to a remote monitoring system. • IS-485EXI: The Liebert® IntelliSlot™ 485 EXI Card provides connection to a Vertiv™ Liebert® SiteLink-E allowing Vertiv™ Liebert® SiteScan™ Web 4.0 monitoring and control of your Liebert equipment. 6.3 Liebert® IntelliSlot™ Web Card—Optional An optional web card is available that provides remote access to the UPS.
Vertiv™ Liebert® EXM UPS User Manual 6.4.1 Vertiv™ Liebert® IntelliSlot™ Relay Card Pin Configuration The card has two terminals blocks, TB1 (green, numbered 1-9) and TB2 (black, 10-18), as shown in Figure 6.2 below . Figure 6.2 Pin Location and Numbering Refer to your Liebert product user manual for the pin configuration for the terminal blocks.
Vertiv™ Liebert® EXM UPS User Manual 6.4.2 Vertiv™ Liebert® IntelliSlot™ Relay Card Jumper Setup The Liebert® IntelliSlot™ Relay Card has five jumpers, P3 through P7, as shown in Figure 6.3 below . Each jumper connects two pins. Figure 6.3 Jumper Location and Numbering By default all five jumpers have shunts installed.
The Vertiv™ Liebert® EXM operates in the modes shown in Vertiv™ Liebert® EXM Operating Modes on the next page . This section describes various kinds of operating procedures under each operating mode, including transfer between operating modes, UPS setting and procedures for turning on/off inverter.
Service—All functions of Administrator plus permission to alter system configuration and change Service PIN; PIN required. 7.3 Default PIN’s Vertiv Services sets PIN’s when setting up the UPS. These default PIN’s may be changed by those with Administrator or Service access (see above). Default PIN’s are: •...
Page 67
NOTE: This unit refers to some modes and conditions that are set or adjusted using proprietary service software. To take advantage of all the available features for the Liebert® EXM, the unit must be commissioned by a Vertiv authorized engineer.
Page 68
When the Vertiv™ Liebert® EXM to is set to Frequency Converter Mode permits configuring the unit for 50 Hz output, bypass is disabled and battery is optional to support load. This mode can only be enabled at the factory or by Vertiv Services.
Liebert® EXM output voltage. Generator Mode The Liebert® EXM UPS can be set up for operation in Generator Mode by a Vertiv Services engineer. The setup requires connecting J26 Pin 2 to Pin 4. The battery charger is disabled in Generator Mode.
Vertiv™ Liebert® EXM UPS User Manual 7.5.2 Start up in Eco Mode Eco Mode is available only on a single module Vertiv™ Liebert® EXM. Log in as Operator, Administrator, or Service. 2. Touch the Operate tab. 3. Touch Energy Saving Mode Activation Setup.
Page 72
NOTE: Pressing Silence from the Operate tab cancels the audible alarm, but leaves the warning message displayed until the appropriate condition is rectified. 5. Open the Vertiv™ Liebert® MBC door to gain access to the Bypass Isolation Breaker (BIB), Maintenance Bypass Breaker (MBB) and Maintenance Isolation Breaker (MIB).
2. Open the Vertiv™ Liebert® MBC door to gain access to the BIB, MBB and the MIB. 3. When the Lamp indicator on the Liebert® MBC is illuminated, press and hold the adjacent push button and remove the key from the lock (K0).
5. Open all battery circuit breakers including the internal battery breaker, if applicable. 6. If the MBC is a Vertiv cabinet, open the MIB. If the MBC is a customer issued switchgear or a non Vertiv cabinet, open the breakers that supply power to the critical bus.
After utility power is restored. • If Auto Recovery after EOD Enabling is enabled in the UPS configuration. Set at the factory or by Vertiv Services. • After the Auto Recovery after EOD Delay Time expire. The default delay is 10 minutes.
7.15.1 Battery Undervoltage Warning Before the end of discharge, the Vertiv™ Liebert® EXM displays a low battery warning. After low battery warning, the battery has the capacity for 5 minutes discharging with full load (default time). The Liebert® EXM can be user-configured to display this warning from 3 to 60 minutes before end of discharge.
BYPASS between the normal mode and maintenance bypass mode, or a temporary abnormal operating status. Maintenance UPS shuts down, the load is connects to the mains through the Vertiv™ Liebert® MBC. In this mode the load is not MAINT Mode protected against abnormal input utility power.
Vertiv™ Liebert® EXM UPS User Manual 8 Specifications and Technical Data 8.1 Conformity and Standards The Vertiv™ Liebert® EXM has been designed to conform to the following standards: • Safety UL 1778, 5th Edition, CSA 22.2 107.3-14 Surge IEC 61000-4-5 Criteria B •...
Page 83
(3) 350 Wire sized for operation at 40 °C. NOTE: A Vertiv™ Liebert® BIB is required for shunt trip of the customer supplied breaker for the external DC source. Refer to SL-25656, available at Vertiv’s Web site, www.vertiv.com, for details.
Maintain the UPS cabinets free of foreign materials such as solder, wire cuttings, etc. Call Vertiv Services if you are not sure of the procedures to follow or if you are not familiar with the design or operation of the equipment.
9.2 Limited Life Components The Vertiv™ Liebert® EXM UPS has a design life well in excess of 10 years. Well maintained units can continue to provide economic benefits for 20 years or more. Long life components are used in the UPS wherever practical and cost effective.
Become thoroughly familiar with the equipment, but at no time go beyond the specific procedures in this manual while performing maintenance or correcting a malfunction. If you have any doubt as to what must be done, call Vertiv Services at 800-543-2378 for further instructions.
All Vertiv™ Liebert® EXM models have replaceable filter elements behind the grille in the front of the unit. This element can be changed with the UPS operating by opening the outer door. The Liebert® EXM’s air filters are washable and reusable. One set of air filters is shipped with each Liebert®...
9.5 Reporting a Problem If a problem occurs within the UPS, review all alarm messages along with other pertinent data. This information should be given to the Vertiv Services dispatcher. Call 800-543-2378 to report a problem or to request assistance. 9.6 Corrective Actions...
X - Means the content of the hazardous substances in at least one of the average quality materials of the part is outside the limits specified in SJ/T11363- 2006. Vertiv has been committed to the design and manufacturing of environment-friendly products. It will reduce and eventually eliminate the hazardous substances in the products through unremitting efforts in research. However, limited by the current technical level, the following parts still contain hazardous substances due to the lack of reliable substitute or mature solution: All solders in the products contain lead.
Input phase sequence is reversed. Contact Vertiv Services at 800-543-2378 for assistance. Soft Start Fail Rectifier could not start due to low DC bus voltage. Contact Vertiv Services at 800-543-2378 for assistance. This alarm is triggered by an inverter software routine when the amplitude or frequency of bypass voltage is beyond the normal range.
Page 98
Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and seek any possible measurements. Contact Vertiv Services at 800-543-2378 for assistance. This alarm indicates a fault condition exists within the inverter. Contact Vertiv Services at 800-543-2378 for Inverter Fault assistance.
Page 99
Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high. Check whether there is a fault in rectifier side. If no, then check whether overload occurs. DC Bus Overvoltage Restart the inverter after resetting the fault. If fault does not clear, contact Vertiv Services at 800-543-2378 for assistance. LBS Active The LBS setting is active.