Vertiv Liebert EXM MBC User Manual
Vertiv Liebert EXM MBC User Manual

Vertiv Liebert EXM MBC User Manual

480 v, 50-250 kva, 60 hz
Hide thumbs Also See for Liebert EXM MBC:

Advertisement

Quick Links

Liebert® EXM MBC
User Manual
480 V, 50-250 kVA, 60 Hz

Advertisement

Table of Contents
loading

Summary of Contents for Vertiv Liebert EXM MBC

  • Page 1 Liebert® EXM MBC User Manual 480 V, 50-250 kVA, 60 Hz...
  • Page 2 The products covered by this instruction manual are manufactured and/or sold by Vertiv. This document is the property of Vertiv and contains confidential and proprietary information owned by Vertiv. Any copying, use, or disclosure of it without the written permission of Vertiv is strictly prohibited.
  • Page 3: Table Of Contents

    2.4 Positioning 2.4.1 Moving the cabinets 2.4.2 Clearances 2.4.3 Floor installation/anchoring 2.5 Cable Entry 2.6 Power Cables 2.6.1 Power cable connection procedure 3 Installation Drawings 4 Specifications 4.1 Electrical Characteristics 4.2 Torque Requirements Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 4 Vertiv™ Liebert® EXM MBC User Manual This page intentionally left blank Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 5: Important Safety Instructions

    1 Important Safety Instructions 1.1 Save These Instructions This manual contains important instructions that must be followed during installation of Vertiv™ Liebert® EXM 480 V maintenance bypass cabinet (MBC). WARNING! Risk of moving heavy units and tipping hazard. Can cause equipment damage, injury and death.
  • Page 6 Une personne ne devrait jamais travailler seule, même si toute l’alimentation de l’équipement est coupée. Une deuxième personne devrait toujours être présente pour porter assistance ou chercher de l’aide en cas d’accident. Proprietary and Confidential ©2024 Vertiv Group Corp. 1 Important Safety Instructions...
  • Page 7: Mechanical Installation

    UPS. • Verify that the room satisfies the environmental conditions stipulated in the equipment specifications, paying particular attention to the ambient temperature and air exchange system. 2 Mechanical Installation Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 8: Environmental Considerations

    2.3 Environmental Considerations 2.3.1 Room The Vertiv™ Liebert® EXM MBC is intended for indoor installation and must be located in a cool, dry, clean air environment with adequate ventilation to keep the ambient temperature within the specified operating range (see Specifications page 31).
  • Page 9: Clearances

    Exercise extreme care when handling cabinets to avoid equipment damage or injury to personnel. The Vertiv™ Liebert® EXM MBC weight ranges from 225-332 lb. (102-151 kg). Locate center of gravity symbols and determine unit weight before handling each cabinet. Test lift and balance the cabinets before transporting.
  • Page 10 Consider using smaller and paralleled cables for heavy currents as a way of easy installation. Figure 1.1 Cabinet Arrangement—Vertiv™ Liebert® EXM 480 V UPS, Battery Cabinets, 480 V MBC NOTE: The 200 mm and 300 mm maintenance bypass cabinets ship attached to the UPS.
  • Page 11: Power Cable Connection Procedure

    En cas de problème, n’hésitez pas à communiquer avec Vertiv. Pour obtenir les renseignements de contact, consultez la dernière page de ce manuel. NOTE: Proper grounding considerably reduces problems in systems caused by electromagnetic interference.
  • Page 12 (see Table 3.11 on page 35). Ensure correct phase rotation. 7. Connect the control wiring from the Liebert® EXM MBC terminal block TB1 to the Vertiv™ Liebert® EXM UPS Bypass Module (X9, J23, and J26). Tighten the connections to the proper torque (see Table 3.11 on page 35).
  • Page 13 In most installations, the load equipment is connected to a distribution network of individually protected busbars fed by the Vertiv™ Liebert® EXM MBC output rather than being connected directly to the Liebert® EXM MBC itself. Where this is the case, the Liebert® EXM MBC output cables can be rated to suit the individual distribution network demands rather than being fully load rated.
  • Page 14 Vertiv™ Liebert® EXM MBC User Manual This page intentionally left blank Proprietary and Confidential ©2024 Vertiv Group Corp. 2 Mechanical Installation...
  • Page 15: Installation Drawings

    Vertiv™ Liebert® EXM MBC User Manual 3 Installation Drawings Figure 2.1 One Line Diagram, Dual Input, Two Breaker Vertiv™ Liebert® 480 V MBC, 50-250 kVA System Item Description Item Description Battery *UPS AC input 3 wire + GND Output busbar...
  • Page 16 Figure 2.2 Bend Radius—Ground Wires through Bottom Feed, 50-250 kVA System Item Description When Attaching ground wires from the bottom feed, connection must be made to the ground busbar as shown for required bend radius. Ground Busbar Proprietary and Confidential ©2024 Vertiv Group Corp. 3 Installation Drawings...
  • Page 17 Vertiv™ Liebert® EXM MBC User Manual Figure 2.3 One Line Diagram, Single Input, Three Breaker Vertiv™ Liebert® 480 V MBC, 50-250 kVA Item Description Item Description Battery Output busbar *Bypass AC input 3 wire + GND AC output 480 V 3 wire + GND...
  • Page 18 Vertiv™ Liebert® EXM MBC User Manual Figure 2.4 One Line Diagram, Dual Input Four Breaker Vertiv™ Liebert® 480 V MBC, 50-250 kVA Item Description Item Description Output busbar *Rectifier AC input 3 wire + GND AC output 480 V 3 wire + GND...
  • Page 19 Vertiv™ Liebert® EXM MBC User Manual Figure 2.5 Main Components—200 mm Vertiv™ Liebert® EXM 480 V MBC, Two to Four Breakers, 50-100 kVA System Item Description Item Description Ground busbar Left side panel removed Front door removed Right side panel removed Table 2.1 Breaker Configuration—200 mm Liebert®...
  • Page 20 Vertiv™ Liebert® EXM MBC User Manual Table 2.2 Terminal Block Details—200 mm Vertiv™ Liebert® EXM 480 V MBC, Two to Four Breakers, 50-100 kVA System Terminal Block Single Input System Dual Input System Input Bypass Output Output — Rectifier Figure 2.6 Main Components—300 mm Liebert® EXM 480 V MBC, Two to Four Breakers, 150-250 kVA System...
  • Page 21 Vertiv™ Liebert® EXM MBC User Manual Table 2.3 Breaker Configuration—300 mm Vertiv™ Liebert® EXM 480 V MBC, Two to Four Breakers, 150-250 kVA System Liebert® EXM MBC Breaker Configuration Configured Breaker — — — Table 2.4 Terminal Block Details—300 mm Liebert® EXM 480 V MBC, Two to Four Breakers, 150-250 kVA System...
  • Page 22 Vertiv™ Liebert® EXM MBC User Manual Figure 2.7 Outline Drawing—200 mm Vertiv™ Liebert® EXM 480 V MBC, Two to Four Breakers, 50-100 kVA System Item Description Item Description Cable entry area 5.3 in. x 7.3 in. (135 mm x 185 mm) Cable entry area 8.3 in.
  • Page 23 7. Copper cables only are recommended. 8. All wiring is to be in accordance with national and local electrical codes. Figure 2.8 Outline Drawing—300 mm Vertiv™ Liebert® EXM 480 V MBC, Two to Four Breakers, 150-250 kVA System 3 Installation Drawings...
  • Page 24 7. Copper cables only are recommended. 8. All wiring is to be in accordance with national and local electrical codes. Figure 2.9 Terminal Details—200 mm Vertiv™ Liebert® EXM 480 V MBC, Four Breakers, 50-100 kVA System Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 25 Rectifier input (TB4) See detail A Left side panel removed Front door removed Right side panel removed Table 2.5 Breaker Configuration—200 mm Vertiv™ Liebert® EXM 480 V MBC, Four Breaker System Liebert® EXM MBC Breaker Configuration Configured Breaker — —...
  • Page 26 Vertiv™ Liebert® EXM MBC User Manual Figure 2.10 Terminal Details—300 mm Vertiv™ Liebert® EXM 480 V MBC, Four Breaker System, 150-250 kVA Item Description Item Description Conduit landing Ground busbar TB4-Dual input systems Bottom view Top view Right side panel view...
  • Page 27 3. All wiring is to be in accordance with national and local electrical codes. 4. If the MBC is attached to the UPS, Vertiv will supply the interconnection cables. Table 2.7 Breaker Configuration—300 mm Vertiv™ Liebert® EXM 480 V MBC, Four Breaker System Liebert®...
  • Page 28 Vertiv™ Liebert® EXM MBC User Manual Figure 2.11 Control Wiring Diagram, Vertiv™ Liebert® EXM 480 V MBC, Two Breakers Item Description X9J24, X9J23, X9J26 Proprietary and Confidential ©2024 Vertiv Group Corp. 3 Installation Drawings...
  • Page 29 Vertiv™ Liebert® EXM MBC User Manual Figure 2.12 Control Wiring Diagram, Vertiv™ Liebert® EXM 480 V MBC, Three Breakers Item Description X9J24, X9J23, X9J26 3 Installation Drawings Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 30 Vertiv™ Liebert® EXM MBC User Manual Figure 2.13 Control Wiring Diagram, Vertiv™ Liebert® EXM 480 V MBC, Four Breakers Item Description X9J24, X9J23, X9J26 Proprietary and Confidential ©2024 Vertiv Group Corp. 3 Installation Drawings...
  • Page 31 Vertiv™ Liebert® EXM MBC User Manual Figure 2.14 Vertiv™ Liebert® EXM 480 V MBC, Key Interlock Control Wiring 3 Installation Drawings Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 32 Vertiv™ Liebert® EXM MBC User Manual Figure 2.15 Solenoid Key Release Unit, 200 mm Vertiv™ Liebert® EXM 480 V MBC Item Description Fuseblock for SKRU NOTE: Solenoid key release unit is mounted between the BIB and MBB breakers. Proprietary and Confidential ©2024 Vertiv Group Corp.
  • Page 33 Vertiv™ Liebert® EXM MBC User Manual Figure 2.16 Solenoid Key Release Unit, 300 mm Vertiv™ Liebert® EXM 480 V MBC Item Description Fuseblock for SKRU NOTE: Solenoid key release unit is mounted between the BIB and MBB breakers. 3 Installation Drawings...
  • Page 34 Vertiv™ Liebert® EXM MBC User Manual This page intentionally left blank Proprietary and Confidential ©2024 Vertiv Group Corp. 3 Installation Drawings...
  • Page 35: Specifications

    Vertiv™ Liebert® EXM MBC User Manual 4 Specifications Table 3.1 Vertiv™ Liebert® EXM 480 V MBC Specifications Model Size 50-100 kVA 150-250 kVA Input Parameters Input voltage to bypass, VAC 480 V, 3-phase, 3-wire Input current, AAC Refer Table 3.1 aboveto Table 3.7 on page 33...
  • Page 36 Vertiv™ Liebert® EXM MBC User Manual Table 3.2 Dimensions for Vertiv™ Liebert® EXM 480 V UPS with Vertiv™ Liebert® EXM 480 V MBC UPS Rating, kVA Components 50-100 200-250 Dimensions, W x D x H, in. (mm) 23.6 X 39.5 X 78.75 23.6 X 39.5 X 78.75...
  • Page 37: Electrical Characteristics

    AC input, bypass and AC output. Recommended cable sizes are suitable for operation at a maximum temperature of 104 °F (40 °C). Table 3.5 Vertiv™ Liebert® EXM 480 V MBC Input Currents, Single Input, Main Voltage 3- System Input Recommended 75 °C Wire...
  • Page 38 Vertiv™ Liebert® EXM MBC User Manual Table 3.8 Vertiv™ Liebert® EXM 48O V MBC Output Currents Voltage 3- System Output Recommended 75 °CWire Copper Aluminum Current MIBA, Phase Upstream Current A, Bolt Size Rating kVA Wire Wire 60 Hz Maximum...
  • Page 39: Torque Requirements

    4.2 Torque Requirements All electrical connections must be tight. Table 3.11 below and Table 3.12 below provide the torque values for the connections to the Vertiv™ Liebert® EXM 480 V MBC. Use these values unless the equipment is labeled otherwise.
  • Page 40 Vertiv™ Liebert® EXM MBC User Manual This page intentionally left blank Proprietary and Confidential ©2024 Vertiv Group Corp. 4 Specifications...
  • Page 41 Vertiv™ Liebert® EXM MBC User Manual...
  • Page 42 Vertiv.com | Vertiv Headquarters, 505 N Cleveland Ave, Westerville, OH 43082 USA ©2024 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp.