Table 3.5 Settings Available at the Display Panel (continued)
Tab
Settings
Shared Battery
Local Battery total AH
Low Battery Time
Battery Replaced Time
Battery Test Interval
Battery Test Weekday
Battery
Battery Test Time
Battery Series
Discharge Protect Time
Equalize Charge Enable
Temperature Compensation Disable, Enable
Replace Battery
Language
Date
Time
Display Orientation
Monitor
Audible Alarm
UPS Comm Address
Control Port Protocol
Modbus Address
Change Settings Password

3.4.1 Changing the Password

The default password is 111111 (six ones). You must use the current password to change the password.
NOTE: We recommend that you change the password from the default to protect your system and
equipment. Record the new password and store it in an accessible location for later retrieval.
1.
At the main menu, select the Settings icon, and press Enter.
2. At the password prompt, use the up-arrow to select the first digit, press the down-arrow to
move to the next digit, repeat for each digit, then press Enter to access the settings.
3. Use the arrow buttons to select the Monitor tab, then press Enter.
3 Operation and Display Panel
Parameter range
Disable, Enable
9 - 36
2 – 30 minutes
YYYY-MM-DD HH:MM:SS
Disable, 8, 12, 16, 20, 26 weeks
Sunday, Monday, Tuesday, Wednesday, Thursday, Friday, Saturday Wednesday
HH:MM:SS
24, 32
1 – 4320 minutes
No, Yes
By HMI Interface Button
English, Chinese, French, Portuguese, Spanish
YYYY-MM-DD
HH:MM:SS
Auto rotate, Horizontal, Vertical
Disable, Enable
01
Modbus, Sensor
1 – 128
0 – 9, must be six digits in length
Default setting
Disable
9
2
2000-01-01 00:00:00
Disable
00:00:00
32
4320
No
Enable
N/A
English
2016-10-01
00:00:00
Auto Rotate
Enable
01
Sensor
1
111111
39