Item
Display Format
Switches the input format of "H/W LED Information" and "H/W SW Information".
INIT.
Indicates the statuses of the LEDs on the E71.
OPEN
ERR.
H/W LED
COM. ERR.
Information
Indicates the connection statuses of the connection numbers 1 to 16.
BUF1 to
BUF16
NET NO.
Indicates the network No. of the E71.
GRP NO.
Indicates the group No. of the E71.
ST NO.
Indicates the station number of the E71.
Indicates the mode of the E71.
MODE
Indicates the operating status of the E71, which has been set with a programming tool.
H/W SW
Information
1) Communication data code setting
CONFIG
2) Initial/open method setting
3) TCP Existence confirmation setting
0000: Off
0001: On
0000: Open not completed
0001: Open completed
0000: Online
0001: Offline
0002: Self-loopback test
0003: H/W test
b15
to
-
0: Communications in a binary code
1: Communications in an ASCII code
0: No parameter setting
(start up according to the sequence program)
1: Parameter setting
(start up according to the parameters)
0: Use the Ping
1: Use the KeepAlive
Description
b9 b8
b7 b6 b5 b4 b3
1/0
-
1/0
1/0
1/0
-
6)
5)
4)
3)
4) Send frame setting
0: Ethernet frame
1: IEEE 802.3 frame
5) Setting of write enable/disable at RUN time
0: Disable
1: Enable
6) Initial timing setting
0: Do not wait for OPEN
(Communications impossible at STOP time)
1: Always wait for OPEN
(Communication possible at STOP time)
CHAPTER 14 TROUBLESHOOTING
b2 b1
b0
1/0
1/0
-
2)
1)
14
239