Error
code
When another station was accessed, the remote
C202
H
password could not be unlocked.
C203
System error (The OS detected an error.)
H
The device is different from the one requesting the
C204
H
remote password unlock.
When another station was accessed, the remote
C205
H
password could not be unlocked.
C206
System error (The OS detected an error.)
H
C207
The file name has too many characters.
H
A response could not be received within the response
C300
H
monitoring timer value.
D000
H
to
(Errors detected by CC-Link IE Field Network)
DFFF
H
E000
H
to
(Errors detected by CC-Link IE Controller Network)
EFFF
H
F000
H
(Errors detected by the MELSECNET/H and
to
MELSECNET/10 network system)
FFFF
H
Remark
The error codes listed in the table include those returned to the connected device. Each buffer memory may also store the
error numbers of the response messages returned from the connected device. If an error code other than those listed is
stored, check the manual for the connected device and the response message from the connected device.
236
Error description
• When accessing another station, do not set the remote password
on the relay station or access station or do not execute the remote
password check on them.
• Follow the procedure below.
(1) Check if the Ethernet module, the power supply module, and the
CPU module are properly connected.
(2) Check if the operating environment of the Ethernet module
conforms to the general specifications of the CPU module.
(3) Check if the power capacity is sufficient.
(4) Check if the hardware is normal according to the manual for each
module.
If the actions above do not solve the problem, please consult your
local Mitsubishi representative.
• Request the lock process of the remote password from the
connected device that requested the unlock process of the remote
password.
• When accessing another station, do not set the remote password
on the relay station or access station or do not execute the remote
password check on them.
• Follow the procedure below.
(1) Check if the Ethernet module, the power supply module, and the
CPU module are properly connected.
(2) Check if the operating environment of the Ethernet module
conforms to the general specifications of the CPU module.
(3) Check if the power capacity is sufficient.
(4) Check if the hardware is normal according to the manual for each
module.
If the actions above do not solve the problem, please consult your
local Mitsubishi representative.
• Name the file with 255 characters or less.
• Check the operation of the connected device.
• Correct the response monitoring timer value.
• Refer to the manual for each module.
• Refer to the manual for each module.
• Refer to the MELSECNET/H or MELSECNET/10 network system
reference manual, and take corrective action.