Mitsubishi Melsec-L Series User Manual page 220

Ethernet interface module
Hide thumbs Also See for Melsec-L Series:
Table of Contents

Advertisement

Error
code
When "ASCII Code" has been selected in the
communication data code setting in the Ethernet
C050
operation setting, ASCII code data which cannot be
H
converted into binary code data has been sent from the
connected device.
The number of read/write points is outside the allowable
C051
H
range.
The number of read/write points is outside the allowable
C052
H
range.
The number of read/write points is outside the allowable
C053
H
range.
The number of read/write points is outside the allowable
C054
H
range.
The number of file data read/write points is outside the
C055
H
allowable range.
• The read/write request exceeds the largest address.
C056
H
• The address is 0.
The request data length does not match with the
C057
H
number of data in the character (a part of text).
The request data length after the ASCII/binary
C058
conversion does not match with the number of data in
H
the character (a part of text).
Incorrect designation of the command and
C059
H
subcommand
The Ethernet module cannot read/write data from/to the
C05A
H
specified device.
The Ethernet module cannot read/write data from/to the
C05B
H
specified device.
Incorrect request (For example, a request for data
C05C
H
read/write in bit units has been issued to a word device.)
C05D
The monitor registration is not performed.
H
The communication time between the Ethernet module
C05E
and the programmable controller CPU exceeded the
H
CPU monitoring timer value.
This request cannot be executed to the target
C05F
H
programmable controller.
Incorrect request (For example, incorrect data was
C060
H
specified for bit devices.)
The request data length does not match with the
C061
H
number of data in the character (a part of text).
When writing was prohibited while the CPU was
running, data has been written to the remote I/O station
C062
H
using the MC protocol (with a QnA-compatible 3E frame
or 4E frame).
218
Error description
• Select "Binary Code" in the Ethernet operation setting. Then
restart the Ethernet module to perform communications again.
• Check and correct the data sent from the connected device and
send it again.
• Correct the number of read/write points and send the data to the
Ethernet module again.
• Correct the number of read/write points and send the data to the
Ethernet module again.
• Correct the number of read/write points and send the data to the
Ethernet module again.
• Correct the number of read/write points and send the data to the
Ethernet module again.
• Correct the number of read/write points (or the number of bytes)
and send the data to the Ethernet module again.
• Correct the start address or the number of read/write points and
send the data to the Ethernet module again. (Make sure that the
request does not exceed the largest address.)
• Check and correct the text or requested data length of the Qn
header. Then send the data to the Ethernet module again.
• Check and correct the text or requested data length of the Qn
header. Then send the data to the Ethernet module again.
• Correct the request details.
• Check the device for read/write.
• Check the device for read/write.
• Correct the request details and send it to the Ethernet module
again. (For example, change the subcommand.)
• Register the monitoring data and perform monitoring.
• Increase the CPU monitoring timer value.
• Check that the programmable controller CPU is operating
normally.
• Correct the network number or PC number.
• If the destination is a station with a different network number,
correct the routing parameter setting.
• If the destination is a station with a different network number,
check if the network number is not in use.
• Correct the network number or PC number.
• Correct the read/write request details.
• Correct the request details and send it to the Ethernet module
again. (For example, correct the data.)
• Check and correct the text or requested data length of the Qn
header. Then send the data to the Ethernet module again.
• To write data to the remote I/O station using the MC protocol (with
a QnA-compatible 3E frame or 4E frame), select "Enable Write at
RUN time" in the Ethernet operation setting.
Action