13.2
Parameter Settings for Using Dedicated Instructions
When using dedicated instructions, set the parameters of each function.
13.2.1
When using data link instructions
When using data link instructions, set the following parameters.
• Station No. <-> IP information setting
• Routing parameters setting
For details on the settings, refer to the following.
MELSEC-Q/L Ethernet Interface Module User's Manual (Application)
13.3
Precautions for Dedicated Instructions
This section describes precautions for using dedicated instructions.
(1) When changing data specified by dedicated instructions
Do not change any data (e.g. control data) until execution of the dedicated instruction is completed.
(2) When the dedicated instruction is not completed
Check that "Online" has been set under "Mode" in the network parameter window. Dedicated instructions cannot
be executed during offline.
(3) Securing service process time
When accessing a programmable controller on another station using a data link instruction during the Ethernet
diagnostics, execution of the instruction may be delayed. Take the following measures to execute the data link
instruction after the Ethernet diagnostics.
• Execute the COM instruction.
• Reserve time for a communication process for 2 to 3 ms. Use a programming tool for the setting.
Project window
System" tab
(4) Specifying the first argument of a dedicated instruction (Un)
The first argument of a dedicated instruction (Un) can be also specified with double quotation marks (" ").
156
[Parameter]
[PLC Parameter]
"Service Processing Setting" under the "PLC