14.7.3

Error codes stored in the buffer memory

The following table lists the error codes stored in each buffer memory area when an error occurs. For the buffer
memory areas where these error codes are stored, refer to the descriptions of the corresponding buffer memory area.
(
Page 33, Section 3.5.2)
Error
code
00
H
02
H
0050
H
0051
H
0052
H
The error details and how to troubleshoot the problem are the same as those for the end code returned to the connected device
0054
H
in data communications. (
0055
H
0056
H
0057
H
0058
H
0059
H
• The CPU module and the Ethernet module cannot
communicate.
005B
H
• The programmable controller CPU cannot process
the request from the connected device.
• The communication time between the CPU module
0060
and the Ethernet module exceeded the CPU
H
monitoring timer value.
• In communications using a fixed buffer, the remote
0063
password of the port for the destination Ethernet
H
module is in the lock status.
This request cannot be specified in connection with the
00A0
H
connected device.
Contents of the request cannot be analyzed because
00A1
H
the text length or request data length is too short.
00A2
This request cannot be processed.
H
3E8
H
to
(Errors detected by a programmable controller CPU)
4FFF
H
7000
H
(Errors detected by a module such as a serial
to
communication module)
7FFF
H
B000
H
to
(Errors detected by a CC-Link module)
BFFF
H
• The IP address setting value of the E71 for the initial
process is incorrect.
C001
H
• The setting value of the subnet mask field for the
router relay function is incorrect.
214
Error description
Page 210, Section 14.7.1)
• Check the error code appended to the end code and correct the
error.
• Increase the CPU monitoring timer value.
• After unlocking the remote password using the MC protocol,
perform communications using a fixed buffer.
• Exclude ports used for communications using a fixed buffer from
the targets of the remote password check.
• Correct the request details.
• Correct the open setting.
• Check and correct the text length or request data length of the Qn
header. Then send data to the Ethernet module again.
• Correct the request details and command.
• Refer to the troubleshooting section of the user's manual
(hardware design, maintenance and inspection) for the CPU
module used, and take corrective action.
• Refer to a manual such as a serial communication module user's
manual, and take corrective action.
• Refer to the CC-Link System Master/Local Module User's Manual,
and take corrective action.
• Correct the IP address. Set the class to A/B/C.
• Correct the subnet mask.
Action