Connecting
6.1 Wiring
6.1.7

Wiring the front connector

The following figure shows how the cables are routed to the front connector and how to
suppress line interference through the use of the shield connecting element.
Figure 6-16
Connecting cables
Flexible cable, cross-section 0.25 to 1.5 mm
Ferrules are not required.
You can use ferrules without an insulating collar in accordance with DIN 46228, Form A long
version.
You can connect two cables of 0.25 to 0.75 mm
Note
To achieve optimum interference suppression, a shielded cable must be used for connection
of measuring inputs or external zero mark.
Required Tools
3.5-mm screwdriver or power screwdriver
114
Wiring the front connector
2
each in one ferrule.
2
Operating Instructions, 11/2016, A5E33441428B
SIMOTION C