5 settings

5.1 Password protection

All easy settings carried out on the device require the use of the button field
and display. Alternatively, you can carry out all easy settings with the
easySoft programming software.
The easy can be protected by a password against unauthorized access.
In this case the password consists of a value between 0001 and 9999. You
can use the number combination 0000 to delete a password.
Default settings:
0000, no password present and none active, circuit diagram
area selected.
Password protection inhibits access to selected areas. The System menu is
always protected when a password is activated.
The password can protect the following entries and areas:
Start or modification of the program
Transfer of a circuit diagram to or from a memory card (Display variants).
the transfer of a circuit diagram from and to the memory card
Change of the RUN or STOP mode.
Calling and modification of function block parameters.
All settings of the real-time clock.
Modifications of all system parameters.
Communication with the individual device.
Disabling of the password delete function.
A password that has been entered in easy is transferred to the
memory card together with the circuit diagram, irrespective of
whether it was activated or not.
If this easy circuit diagram is loaded back from the memory
card, the password will also be transferred to easy and is
activated immediately.
Operating instructions 05/10 MN05013003Z-EN www.eaton.com