Remote Device Station Common Specification; Cyclic Transmission Signals; Cyclic Transmission Signal Definitions - Renesas R-IN32 Series User Manual

Cc-link remote device station
Table of Contents

Advertisement

R-IN32 Series CC-Link Remote device station
10.

Remote Device Station Common Specification

10.1

Cyclic Transmission Signals

10.1.1

Cyclic Transmission Signal Definitions

The I/O points of the remote device station are divided into a user area and a system area.
The final 16 bits of RX and RY are reserved as system areas.
The following lists the number of user area points according to the number of occupied stations.
1 occupied station: 16 bits
2 occupied stations: 48 bits
3 occupied stations: 80 bits
4 occupied stations: 112 bits
Link Input
RXm0
User area
:
:
:
:
RXs0
Reserved
RXs1
RXs2
RXs3
RXs4
RXs5
RXs6
RXs7
RXs8
Initial data processing request flag
RXs9
Initial data setting complete flag
RXsA
Error status flag
RXsB
Remote ready (required)
RXsC
Reserved
RXsD
RXsE
RXsF
: m: A number derived from the station number setting.
Remark
s: Indicates the RX/RY system area occupied by the slave station.
R18UZ0056EJ0102
Dec. 28, 2018
Signal Name
10. Remote Device Station Common Specification
Link Output
RYm0
User area
:
:
:
:
RYs0
Reserved
RYs1
RYs2
RYs3
RYs4
RYs5
RYs6
RYs7
RYs8
Initial processing complete flag
RYs9
Initial setting request flag
RYsA
Error set request flag
RYsB
Reserved
RYsC
RYsD
RYsE
RYsF
Signal Name
Page 40 of 83