R-IN32 Series CC-Link Remote device station
10.1.2

System Area Details

(1) RXsB (Remote Ready)
Indicates that data transmission/reception is possible between the master station and user program of the remote device
station.
Turn this signal ON after power ON or hardware reset.
Be sure to implement this signal.
:
Caution
This signal turns OFF when master station data transmission/reception with the user program
is not possible due to an error.
Figure 10.1 RXsB (Remote Ready)
(2) RXs8/RYs8 (Initial Data Processing Request / Processing Complete Flag)
Used when the remote device station requests the user program to execute initial data processing after remote device
power ON or hardware reset.
:
Caution
Remote ready (RXsB) is turned ON after initial data processing is completed.
RXs8
RYs8
RXsB
Figure 10.2 RXs9/RYs9 (Initial Data Processing Request / Processing Complete Flag)
R18UZ0056EJ0102
Dec. 28, 2018
RXsB
Power ON
Initial data processing
10. Remote Device Station Common Specification
Enabled from this point
Enabled from this point