7. EtherNet/IP Connection Procedure

This section describes the procedure for connecting the PLC and the Controller via
EtherNet/IP using the "procedure for using configuration files".
This document explains the procedures for setting up the Controller and the PLC from the
factory default setting. For the initialization, refer to Section 8 Initialization Method.
■Setting Overview
The following figure shows the relationship between the processes to operate the
EtherNet/IP tag data link using the "procedure for using configuration files".
Configuration file
Importing the
project file
Transferring
the project data
Precautions for Correct Use
Prepare the latest "Sysmac Studio project file" and "Network Configurator v3 network
configuration file" from OMRON in advance.
(To obtain the files, contact your OMRON representative.)
Sysmac Studio
project file
Personal computer
Sysmac Studio
Controller
7. EtherNet/IP Connection Procedure
Network Configurator v3
network configuration file
Network Configurator
Transferring the tag
data link parameters
Reading the network
configuration file
Destination
device
9