9.3. Associating the Tag Data Links

Tag data link parameters are required to perform tag data links with a destination device.
Follow the procedures below to associate the tag data links.
(1)Use the Sysmac Studio to define the global variables to publish on the network.
Store the created global variables in a CSV file to use in the Network Configurator.
(2)Read the CSV file (tag list) created in step 1 to the Network Configurator.
(3)Make a single tag set that includes the tag lists.
(4)Link the tag set with the destination device information and create tag data link
parameters.
The numbers shown in the tables below correspond to the steps above.
■Output area (Controller → PLC)
Controller setting
(Set with Sysmac Studio.)
(1)
Global variable
EIP002_D1010
0_OUT
■Input area (Controller ← PLC)
Controller setting
(Set with Sysmac Studio.)
(1)
Global variable
EIP002_D1000
0_IN
9. Appendix 1 Detailed Settings of the Tag Data Links
Data link table setting
(Set with Network Configurator.)
Tag set:
EIP002_OUT
(3)
Tag list
WORD
EIP002_D10
[10]
(2)
100_OUT
Data link table setting
(Set with Network Configurator.)
Tag set:
EIP002_IN
(3)
Tag list
WORD
EIP002_D10
[10]
(2)
000_IN
Destination device
information
20byte
D10100-[20Byte]
(4)
*Refer to 9.2 for
(20byte)
details.
Destination device
information
20byte
D10000-[20Byte]
(4)
*Refer to 9.2 for
(20byte)
details.