Table 4-8: Monitor Sub-Menu - Honeywell SmartLine SLG 700 User Manual

Level transmitter guided wave radar
Hide thumbs Also See for SmartLine SLG 700:
Table of Contents

Advertisement

This table describes the Advanced Display menu's "Monitor" sub-menu. All items are Read-
Only. Refer to troubleshooting for resolutions.
<Return> Return to the Level 1 menu
Level 2
Level 3
<Return>
Active Diags (R)
Sensor Module (R)
Comm Module (R)
Sensor Comm (R)
Measurement (R)
Critical Diag
Reset Required (R)
Soft Reset
Detail Diag
Sensor Int RAM (R)
Sensor Ext RAM (R)
Sensor Flash CRC (R)
Sensor Pwr Vosc (R)
Sensor Pwr 2.5V (R)
Sensor Pwr 3.3V (R)
Sensor Pwr Accum (R)
Sensor Code Flow (R)
Sensor Oscillator (R)
Factory Mode (R)
Page 114

Table 4-8: Monitor sub-menu

Status
# #
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
Yes
No
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
OK
FAULT
Yes
No
SLG 700 SmartLine Level Transmitter User's Manual
Description
FAULT: There is a problem with the Sensor.
FAULT: There is a problem with the
Communications Module (HARTor FF), There are
one of the following failures:
RAM Failure: Restart the device. If error continues,
replace the HART communication board.
ROM Failure: Reflash / reload the HART firmware.
If error continues, replace the HART
communication board.
V
Failure: If the power accumulator (PA) fault is
CC
not detected, change the HART communication
board.
FAULT: There is a problem with the interface
between the Sensor and the Electronics Module.
FAULT: There is a problem with the PV
measurement.
FAULT: A parameter has been changed that
requires a transmitter restart.
Perform transmitter restart
Yes: All menu items to Factory Mode are available.
No: The menu options end with Detail Diag.
FAULT: Sensor Internal RAM is Bad
FAULT: Sensor Internal RAM is Bad
FAULT: Sensor Flash CRC is Bad
FAULT: The Vosc measurements are out of range,
resetting the device if the problem persists, replace
the Sensor Housing.
FAULT: Sensor Power Supply 2.5V is Bad
FAULT: Sensor Power Supply 3.3V is Bad
FAULT: Power Accumulator Board is Bad
FAULT: Sensor Execution is not working as
intended
FAULT: Sensor Oscillator Control Status is Bad
Yes: Sensor is in Factory Mode
No: Sensor is in User Mode
Revision 8