Transmitter Menu; Menu Tree; Table 9 Menu Tree - Honeywell OneWireless XYR 6000 User Manual

Temperature and temperature/discrete input transmitter
Hide thumbs Also See for OneWireless XYR 6000:
Table of Contents

Advertisement

5. Operation

5.5. Transmitter menu

5.5
Transmitter menu

Menu tree

At the PV display, press Enter to access the menus. To interact with the menus use the Device Local
Configuration onscreen buttons (page 32) or the buttons on your PDA.
Menu item
CAL
CH-1
CH-2
CH-3
RADIO
PRI RSSI
SEC RSSI
WFN ID
DEV ADD
TX POWER
28
OneWireless XYR 6000 Temperature and Temperature/Discrete Input Transmitter User's Manual
Description
Calibration menu. May be password-protected. See Table 10 on
page 32 for password number entry.
Channel 1.
Channel 2.
Channel 3.
CAL RSTR
Restores selected channel to factory calibration.
USER CAL
Lets you calibrate selected channel's low and high points.
CAL CLR
Clear the factory and user calibration.
EXIT
Exits calibration menu and returns to PV display.
Radio menu
Primary receive signal strength. Read only. Signal strength 00 is too
weak to connect to the network.
Displayed Value
00
01
02
03
04
05
06
07
08
09
Secondary receive signal strength. Same as PRI RSSI. Read only.
Wireless Field Network ID. Read only.
Device address. Read only.
Radio transmit power. Read only.

Table 9 Menu tree

Value dBm
< -86
-86 to -81
-80 to -75
-74 to -69
-68 to -63
-62 to -57
-56 to -51
-50 to -45
-44 to -11
≥ -10
Rx Margin dB
< 10
10 to 15
16 to 21
22 to 27
28 to 33
34 to 39
40 to 45
46 to 51
52 to 85
Saturation
Rev. 3
6/24/08

Advertisement

Table of Contents
loading

Table of Contents